Catalog No./Item Description/Specifications
5400TB Two- Compartment Base
Two equal compartments –
Base accepts single or Twin
Snap Cover. 5400TB Series
Raceway available in 8' (2.44m)
lengths with pre-punched
mounting holes
5400C Full Width Cover – Use with
5400TB. Available in 8' (2.44m)
lengths.
5400TC Twin Snap Cover – Use with
5400TB Series Raceway in Twin
Snap applications. Order
separate cover for each
compartment. Available
in 8' (2.44m) lengths.
5400TWC Twin Snap Cover Wire Clip
Retains wires in raceway.
Catalog No./Item Description/Specifications
MXN2F21 Entrance End Fitting
For feeding corner drop
raceway from larger conduits.
Has concentric 3/4", 1", and
1 1/2" trade size KOs.
MXN2A08 Corner Drop Raceway
Base and Cover – Used as
a vertical corner feed drop
to horizontal run of 5400 or
40N2 Series Raceways.
Two compartments. Packaged
with base and cover.
MXN2FWC Wire Clip – Retains wires
in MXN2A08 Corner
Drop Raceway.
NOTE: No suffix denotes Ivory finish. Add “-WH” suffix for White finish.
5400 Series Raceway Ordering Information
6 1/8"
(156mm)
3 5/8"
(92mm)
5 1/4"
(133mm)
1 11/16"
(43mm)
8'
(2.44m)
4 31/32"
(126mm)
8'
(2.44m)
2 9/16"
(65mm) Each
8'
(2.44m)
2"
(51mm)
3 5/16"
(84mm)
8'
(2.45m)
2 5/8"
(67mm)
2 "
(51mm)
5400T Series Raceway & MXN Series Raceway Wire Fill Capacity Charts (continued)
WIRE SIZE O.D. (Approx. Dia.) NO. OF CONDUCTORS
CABLE/WIRE SIZE Inches (mm) EACH COMPARTMENT
14 AWG 0.111 (2.8) 16
12 AWG 0.130 (3.3) 14
10 AWG 0.164 (4.2) 14
8 AWG 0.216 (5.5) 15
MXN Series Raceway Wire Fill Capacities for Power
O.D. (Approx. Dia.) EA. COMPARTMENT
CABLE/WIRE SIZE Inches (mm) 40% FILL
UNSHIELDED 4-pair, 24 AWG Cat 3 0.190 (4.8) 19
TWISTED PAIR 4-pair, 24 AWG Cat 5e 0.210 (5.3) 16
4-pair, 24 AWG Cat 6 0.250 (6.3) 11
4-pair, 24 AWG Cat 6a* 0.250 (6.3) 5
25-pair, 24 AWG 0.250 (6.3) 4
COAXIAL RG6/U 0.270 (6.9) 9
FIBER ZipCord 0.118 x 0.236 (3 x 6) 20
Round 4-Strand Fiber 0.187 (4.8) 20
Round 6-Strand Fiber 0.256 (6.5) 10
MXN Series Raceway Wire Fill Capacities for Communications
NOTE: Wire fill capacity is reduced to allow for proper conductor bend radius and maximum permissible heat rise.
* Category 6 augmented (6a) cable for 10 gigabit Ethernet – maximum allowed cable diameter
per addenda No. 11 ANSI TIA/EIA 568-B.2.
5 1/4"
(133mm)
3.72 sq. in.
(2400mm
2
)
3.72 sq. in.
(2400mm
2
)
A*
B*
1 3/4"
(44mm)
Total Raceway Capacity is
7.44 sq. in. (4800mm
2
)