2
5517FO
5515
5550A4
5574
5500WCA
5511FO
5500 Series Raceway System Layout
5510
5506
5550
5518
5518FO
5514A
NOTE: Illustration is for showing product applications only.
5500 Series Raceway Wire Fill Capacities
CABLE O.D. (Approx. Dia.) 20% FILL 40% FILL
TYPE CABLE/WIRE SIZE Inches (mm) C A B C A B
Unshielded 4-pair, 24 AWG Cat. 3 0.190 (4.8) 57 18 35 114 37 71
Twisted Pair 4-pair, 24 AWG Cat. 5e 0.220 (5.6) 47 15 29 94 30 58
4-pair, 24 AWG Cat. 6 0.250 (6.3) 33 10 20 66 21 41
4-pair, 24 AWG Cat. 6a 0.354 (8.9) 16 5 10 33 10 20
Telephone 2-pair, 24 AWG 0.140 (3.6) 105 34 65 211 68 131
3-pair, 24 AWG 0.150 (3.8) 92 29 57 184 59 114
4-pair, 24 AWG 0.190 (4.8) 57 18 35 114 37 71
25-pair, 24 AWG 0.410 (10.4) 12 4 7 24 8 15
Coaxial RG58/U 0.195 (5.0) 54 17 33 109 35 67
RG59/U 0.242 (6.1) 35 11 22 70 22 44
RG62/U 0.242 (6.1) 35 11 22 70 22 44
RG6/U 0.270 (6.9) 28 9 17 56 18 35
Twinaxial 100 ohm 0.330 (8.4) 19 6 11 38 12 23
Shielded TYPE 1 0.390 (9.9) 13 4 8 27 8 16
Twisted Pair TYPE 2 0.465 (11.8) 9 3 5 19 6 11
TYPE 3 0.245 (6.2) 34 11 21 69 22 42
Fiber Mini ZipCord 0.079 x 0.157 (2 x 4) 131 42 81 262 85 163
ZipCord 0.118 x 0.236 (3 x 6) 58 18 36 117 37 72
Round 4 Strand Fiber 0.187 (4.8) 59 19 36 118 38 73
Round 6 Strand Fiber 0.256 (6.5) 31 30 19 63 20 39
NOTE: Wire capacity is reduced to allow for proper conductor bend radius and maximum permissible heat rise.
Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
5500 Series Raceway Wire Fill Capacities for Communications
Download this product’s PEP ecopasport
®
environmental product declaration at
www.legrand.us/resources-and-downloads.
This declaration conforms with ISO 14025 and