Installation Manual
Products Covered:
Steel Floor Boxes – 880M1, 880M2, 880M3 (Shallow), and 880S1, 880S2, 880S3 (Deep)
Cast Iron Floor Boxes – 880CM1-1, 880CM2-1, 880CM3-1 (Shallow), and 880CS1-1, 880CS1-NA, 880CS2-1,
880CS2-NA, 880CS3-1, 880CS3-NA (Deep)
Cat No. 880S2 Shown
FLOOR BOX INSTALLATION:
1. Determine box and conduit layout.
2. Remove required knockouts and attach
conduit with fittings.
3. Barrier must be installed if more than
one service is used.
CONCRETE PREPARATION:
1. Install concrete mud cap.
2. Adjust box height to 1/16" [1.59mm]
below screed line.
3. Secure box into position with
screws or rebar and pour concrete.
Legrand/Wiremold electrical systems conform to and should be proper-
ly grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
OmniBox
™
Series Floor Boxes
I N S T A L L A T I O N I N S T R U C T I O N S
I
nstallation Instruction No.: IA0030R3 – Updated June 2012
WIREMOLD
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251
Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
1-800-723-5175 • FAX 905-738-9721
IA0030R3 0612