Installation Manual

AL3300 RACEWAY CABLE FILL CAPACITIES FOR DATA/COMMUNICATION
OD W/O Divider W/Offset Divider W/Half Divider
CABLE/WIRE SIZE [In.] [mm] (4.75 sq. in.) (.95 sq. in.) (2.08 sq. in.)
20%* 40%** 20%* 40%** 20%* 40%**
UNSHIELDED 4-pair, 24 AWG, Cat.5 0.220 [5.6] 24 49 4 9 10 21
TWISTED PAIR 4-pair, 24 AWG, Cat.3 0.190 [4.8] 33 67 6 13 14 29
4-pair, 24 AWG, Cat.6 0.250 [6.3] 19 38 3 7 8 16
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 61 123 12 24 27 54
3-pair, 24 AWG 0.150 [3.8] 53 107 10 21 23 47
4-pair, 24 AWG 0.190 [4.8] 33 67 6 13 14 29
25-pair, 24 AWG 0.410 [10.4] 7 14 1 2 3 6
COAXIAL RG58/U 0.195 [5.0] 31 63 6 12 13 27
RG59/U 0.242 [6.1] 20 41 4 8 9 18
RG62/U 0.242 [6.1] 20 41 4 8 9 18
RG6/U 0.270 [6.9] 16 33 3 6 14
TWINAXIAL 100 Ohm 0.330 [8.4] 11 22 2 4 4 9
SHIELDED Type 1 0.390 [9.9] 7 15 1 3 3 6
TWISTED PAIR Type 2 0.465 [11.8] 5 11 1 2 2 4
Type 3 0.245 [6.2] 20 40 4 8 8 17
FIBER OPTIC Two Standard (Duplex) 0.190 [4.8] 33 67 6 13 14 29
Multimedia, 62.5/125 um
AL3300 Aluminum
Surface Raceway
INSTALLATION INSTRUCTIONS
Installation Instruction No.: INST014 R2 – Updated April 2005
NOTE:* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
2 7/8"
[70mm]
1 7/8"
[48mm]
AL3300 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH OFFSET WITHOUT WITH HALF WITHOUT
DIVIDER OFFSET DIVIDER DIVIDER HALF DIVIDER
WIRE TYPE 6 AWG 10 24 17 33
THWN/THHN 8 AWG 14 33 23 47
10 AWG 28 66 47 95
12 AWG 44 104 74 150
14 AWG 60 140 99 202