Installation Manual

AL5200 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATION
CAPACITY CROSS SECTIONAL AREA
CABLE/WIRE SIZE OD 8.5" [216mm] 4.85" [122mm] 3.78" [89mm] 3.86" [99mm] 4.36" [114mm]
Inches [mm] 20%* 40%** 20%* 40%** 20%* 40%** 20%* 40%** 20%* 40%**
UNSHIELDED 4-pair, 24 AWG,cat.3 0.190 [4.8] 60 20 34 68 26 53 27 54 30 61
TWISTED PAIR 4-pair, 24 AWG,cat.4 0.220 [5.6] 44 89 25 51 19 39 20 40 22 45
4-pair, 24 AWG,cat.5 0.250 [6.3] 34 69 19 39 15 30 17 31 17 35
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 10 221 63 126 49 98 50 100 56 113
3-pair, 24 AWG 0.150 [3.8] 96 193 54 109 42 85 43 87 49 98
4-pair, 24 AWG 0.190 [4.8] 60 120 34 68 26 53 27 54 30 61
25-pair, 24 AWG 0.410 [10.4] 12 125 7 14 5 11 5 11 6 13
COAXIAL RG58/U 0.195 [5.0] 57 114 32 64 25 50 25 51 29 58
RG59/U 0.242 [6.1] 37 74 21 42 16 32 16 33 18 37
RG62/U 0.242 [6.1] 37 74 21 42 16 32 16 33 18 37
RG6/U 0.270 [6.9] 29 59 16 33 13 26 13 26 15 30
TWINAXIAL 100 Ohm 0.330 [8.4] 19 39 11 22 8 17 9 18 10 20
SHIELDED TYPE 1 0.390 [9.9] 14 28 8 16 6 12 6 12 7 14
TWISTED PAIR TYPE 2 0.465 [11.8] 10 20 5 11 4 8 4 9 5 10
TYPE3 0.245 [6.2] 36 72 20 41 20 32 16 32 18 36
FIBER OPTIC Two Standard(Duplex)
Multimode, 62.5/125um 0.190 [4.8] 60 120 34 68 26 53 27 54 30 61
AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH OUT DEVICE
WIRE TYPE 2.4" [61mm] 2.85" [72mm] 3.5" [85mm] 3.9" [99mm] 4.5" [114mm] 4.8" [122mm] 8.5" [216mm]
THWN/THHN #6 18 22 27 30 34 37 65
#8 25 30 37 42 48 51 91
#10 52 62 76 84 98 104 184
#12 82 97 119 113 154 164 290
#14 110 131 161 179 207 220 391
AL5200 Aluminum
Surface Raceway
INSTALLATION INSTRUCTIONS
AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER
CAPACITY OF CROSS SECTIONAL AREA
WITH DUPLEX DEVICE (1.34 Sq.in.)
WIRE TYPE 3.78" [89mm] 3.86" [99mm] 4.36" [114mm] 4.85" [122mm] 8.5" [216mm]
THWN/THHN #6 16 19 24 26 55
#8 23 27 34 37 76
#10 47 55 68 75 155
#12 74 87 108 118 244
#14 99 117 145 159 329
NOTE:* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
8.5 sq. in.
[215.90mm]
5"
[127mm]
2 3/4"
[70mm]
2 3/16"
[56mm]
2"
[51mm]
4.86 sq. in.
[123.19mm]
3.78 sq. in.
[96.01mm]
3.90 sq. in.
[99.06mm]
4.50 sq. in.
[114.30mm]

Summary of content (4 pages)