Cut Sheet

3
ALDS4000 Series Raceway Wire Fill Capacity Charts
CABLE CATEGORY/ O.D. 40% FILL 1/2
TYPE DESIGNATION Inches [mm]
COMPARTMENT
UNSHIELDED 4-pair, 24 AWG Cat 3 0.190 [4.8] 68
TWISTED PAIR 4-pair, 24 AWG Cat 5e 0.210 [5.3] 56
4-pair, 24 AWG Cat 6 0.250 [6.3] 40
4-pair, 24 AWG Cat 6a* 0.354 [8.5] 22
25-pair, 24 AWG 0.360 [9.1] 19
COAXIAL RG6/U 0.270 [6.9] 34
FIBER ZipCord 0.118 x 0.236 [3 x 6] 70
Round 4-Strand Fiber 0.187 [4.8] 71
Round 6-Strand Fiber 0.256 [6.5] 38
* Category 6 Augmented cable for 10 gigabit ethernet – max allowed cable diameter per Addendum 11
to ANSI/TIA-568-B.2.
NOTE: Prewired downward facing
covers are punched in line
for a sleek flush look. Power
conductors are provided in
the lower channel. Additional
wires can be field installed
and should not exceed totals
above. Communications are
to be installed in the top
channel – refer to standard
cable fill chart for capacities.
NOTE: For additional information, refer to the Technical Section of the current version of the Wiremold Catalog.
ALDS4000 Raceway Wire Fill Capacities for Communication
NUMBER OF CONDUCTORS (40% FILL)
WITH DUPLEX/ WITH SURGE/ LARGE SINGLE
WIRE SIZE O.D. WITHOUT RECT. DEVICE GFCI DEVICE RECEPTACLE
THHN/THWN Inches [mm] DEVICES
1.59in.
2
[1025mm
2
] 2.30in.
2
[1485mm
2
] 3.00in.
2
[1935mm
2
]
14 AWG 0.111 [2.8] 200 134 105 76
12 AWG 0.130 [3.3] 146 98 77 56
10 AWG 0.164 [4.2] 92 62 48 35
8 AWG 0.216 [5.5] 53 36 28 20
6 AWG 0.254 [6.5] 38 26 20 15
A
LDS4000 Raceway Wire Fill Capacities for Power
WIRE SIZE O.D. NO OF CONDUCTORS
THHN/THWN Inches [mm] 40% FILL
14 AWG 0.111 [2.8] 30
12 AWG 0.130 [3.3] 22
10 AWG 0.164 [4.2] 14
8 AWG 0.216 [5.5] 8
6 AWG 0.254 [6.5] 6
Prewired ALDS4000 Cover Wire Fill Capacities
with Downward Facing Power & Data Devices
WIRE SIZE O.D. ALDS4011 ALDS4015 ALDS4017 ALDS4018
THHN Inches [mm] 40% 60% 40%** 60%** 40%** 60%** 40%** 60%**
THHN 14 0.111 [2.8] 122 182 49 73 75 112 133 199
12 0.130 [3.3] 89 133 35 53 54 82 97 145
10 0.164 [4.2] 56 84 22 34 34 51 61 92
8 0.216 [5.5] 32 48 13 19 20 30 35 53
6 0.254 [6.5] 23 35 9 14 14 21 25 38
UTP 2-pair, 24 AWG 0.150 [4.8] 67 100 27 40 41 61 73 109
4-pair, 24 AWG Cat 3 0.190 [4.8] 42 62 17 25 25 38 45 68
4-pair, 24 AWG Cat 5e 0.210 [5.3] 34 51 14 20 21 31 37 56
4-pair, 24 AWG Cat 6 0.250 [6.3] 24 36 10 14 15 22 26 39
4-pair, 24 AWG Cat 6a* 0.354 [9.0] 13 20 58812 15 22
25-pair, 24 AWG 0.410 [10.4] 12 17 57711 13 19
Coaxial RG6/U 0.270 [6.9] 21 31 8 12 13 19 22 34
Fiber ZipCord 0.118 x 0.236 [3 x 6] 42 64 17 25 26 39 46 69
Round 4-Strand Fiber 0.187 [4.8] 43 64 17 26 26 40 47 70
Round 6-Strand Fiber 0.256 [6.5] 23 34 9 14 14 21 25 38
* Entrance end fitting fill rate is calculated using backfeed capability and radius inserts. Inserts are removable and fitting can obtain maximum
raceway fill from utilizing end fitting knockouts and removing radius control inserts.
** Calculated using radius control inserts. Inserts are factory installed and may be removed if not required to obtain full raceway capacity.
ALDS4000 Raceway Fittings Wire Fill Capacity Chart