Installation Manual

AL2000 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATION
OD
CABLE/WIRE SIZE [In.] [mm] 20% FILL* 40% FILL**
UNSHELDED 4-pair, 24 AWG, Cat 5 0.220 [5.6] 5 11
TWISTED PAIR 4-pair, 24 AWG, Cat, 3 0.190 [4.8] 7 15
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 14 28
3-pair, 24 AWG 0.150 [3.8] 12 25
4-pair, 24 AWG 0.190 [4.8] 7 15
25-pair, 24 AWG 0.410 [10.4] 1 3
COAXIAL RG58/U 0.195 [5.0] 7 14
RG59/U 0.242 [6.1] 4 9
RG62/U 0.242 [6.1] 4 9
RG6/U 0.270 [6.9] 3 7
TWINAXIAL 100 Ohm 0.330 [8.4] 2 5
SHELDED Type 1 0.390 [9.9] 1 3
TWISTED PAIR Type 2 0.465 [11.8] 1 2
Type 3 0.245 [6.2] 4 9
AL2000 Aluminum
Surface Raceway
INSTALLATION INSTRUCTIONS
AL2000 RACEWAY WIRE FILL CAPACITIES FOR POWER
WIRE TYPE TW THW RHH/RHW THHN/THWN
POWER WIRING 6 AWG 5 5 4 8
WITHOUT DEVICE 8 AWG 9 7 5 12
1.1 sq. in. cross section 10 AWG 20 14 10 24
12 AWG 26 17 16 38
14 AWG 33 21 19 51
POWER WIRING AWG 6 AWG 3 2 2 3
WITH DEVICE 8AWG 4 3 2 6
515 amp devices 10 AWG 5 3 3 8
.8 sq. in. cross section
NOTE:* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict
cross sectional area.
** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.
Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.
All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.
Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.
MAXIMUM CROSS SECTION
1.1 sq. in.
[27mm]
1 7/16"
[37mm]
1 1/8"
[29mm]
.8 sq. in.
[20.3mm]