Installation Manual

2
NOTE: Use No. 8 (5/16", 7.9mm head size) flat head fastener or equivalent to mount base to surface.
NOTE: Grounding: Use ground location when provided or install a suitable ground lug, ring terminal or
locknut and ground bushing.
TYPE UNSHIELDED) TELEPHONE COAXIAL TWINAXIAL SHIELDED FIBER
TWISTED PAIR 24 AWG, No. of Pairs TWISTED PAIR OPTIC
RG58/U RG59/U RG62/U RG6/U 100 OHM TYPE 1 TYPE 2 TYPE 3 Two Strand
(Duplex)
Multimode,
CAT 5 CAT 3 2 3 4 25 RG58/U RG59/U RG62/U RG6/U 100 OHM TYPE 1 TYPE 2 TYPE 3 62.5/125µm
6000 SERIES RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS
TYPE AWG,
THHN/THWN 2/0 1/0 1 2 4 6 8 10 12 14
* Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
6000 SERIES RACEWAY WIRE FILL CAPACITIES FOR POWER WITH DEVICES
O.D. Inches 0.220 0.190 0.140 0.150 0.190 0.410 0.195 0.242 0.242 0.270 0.330 0.390 0.465 0.245 0.190
O.D. (mm) (5.6) (4.8) (3.6) (3.8) (4.8) (10.4) (5.0) (6.1) (6.1) (6.9) (8.4) (9.9) (11.8) (6.2) (4.8)
40% FILL 80 107 198 172 107 23 102 66 66 53 35 25 17 64 107
Divided
40% FILL 161 217 399 348 217 46 206 133 133 107 71 51 36 139 217
Undivided
O.D. Inches 0.532 0.486 0.446 0.384 0.324 0.254 0.216 0.164 0.130 0.111
O.D. (mm) (13.5) (12.3) (11.3) (9.8) (8.2) (6.5) (5.5) (4.2) (3.3) (2.8)
40% FILL 14 17 20 27 38 62 86 149 237 325
Divided
40% FILL 28 34 40 54 76 125 173 300 475 652
Undivided
TYPE AWG,
THHN/THWN 2/0 1/0 1 2 4 6 8 10 12 14
6000 SERIES RACEWAY WIRE FILL CAPACITIES FOR POWER WITHOUT DEVICES
O.D. Inches 0.532 0.486 0.446 0.384 0.324 0.254 0.216 0.164 0.130 0.111
O.D. (mm) (13.5) (12.3) (11.3) (9.8) (8.2) (6.5) (5.5) (4.2) (3.3) (2.8)
40% FILL 11 14 16 22 31 51 71 123 195 268
Divided
40% FILL 22 26 31 43 60 98 135 235 373 512
Undivided