Cut Sheet

5
* Capacity range is calculated at 20% to 40% of raceway area as stated in a proposed revision to the Commercial Building Standard for
Telecommunication Pathways & Spaces, TIA/EIA-569. Actual wire fill capacity may vary based on applications, cable types, and number,
as well as type of fittings. (Fittings may cause additional variances to the fill capacity.)
* For additional information, refer to section T1 of the Buyer’s Guide.
O.D. (Approx. Dia.)
CABLE/WIRE SIZE Inches [mm] 20% FILL 40% FILL
UNSHIELDED 4-pair, 24 AWG Cat. 3 UTP 0.190 [4.8] 5 11
TWISTED PAIR 4-pair, 24 AWG Cat. 5e UTP 0.210 [5.3] 4 9
4-pair, 24 AWG Cat. 6 UTP 0.250 [6.3] 3 6
TELEPHONE 2-pair, 24 AWG 0.140 [3.6] 10 21
3-pair, 24 AWG 0.150 [3.8] 9 19
4-pair, 24 AWG 0.190 [4.8] 5 11
25-pair, 24 AWG 0.410 [10.4] 1 2
COAXIAL RG58/U 0.195 [5.0] 5 11
RG59/U 0.242 [6.1] 3 7
RG62/U 0.242 [6.1] 3 7
RG6/U 0.270 [6.9] 2 5
TWINAXIAL 100 Ohm 0.330 [8.4] 1 3
SHIELDED TYPE 1 0.390 [9.9] 1 2
TWISTED PAIR TYPE 2 0.465 [11.8] 0 1
TYPE 3 0.245 [6.2] 3 7
FIBER Mini ZipCord 0.079 x 0.157 [2 x 4] 13 27
ZipCord 0.118 x 0.236 [3 x 6] 6 12
Round 4 Strand 0.187 [4.8] 6 12
Round 6 Strand 0.256 [6.5] 3 6
2100 Raceway Cable Fill Capacities for Data/Communication*
NUMBER OF CONDUCTORS (40% FILL)
WIRE SIZE O.D. WITHOUT WITH 2127G WITH 2127GA,
THHN/THWN Inches [mm] DEVICES RECEPTACLE GB AND GT
RECEPTACLE
14 AWG 0.111 [2.8] 34 4 9
12 AWG 0.130 [3.3] 25 3 6
10 AWG 0.164 [4.2] 15 2 4
8 AWG 0.216 [5.5] 9
6 AWG 0.254 [6.5] 6
2100 Raceway Wire Fill Capacities for Power*