Installation Manual

2
NOTE: Use No. 8 (5/16", 7.9mm head size) flat head fastener or equivalent to mount base to surface.
NOTE: Grounding: Use ground location when provided or install a suitable ground lug, ring terminal or
locknut and ground bushing.
O.D. (APPROX. DIA.) DIVIDED UNDIVIDED
CABLE/WIRE SIZE Inches (mm) 40% FILL 40% FIL
UNSHIELDED 4-pair, 24 AWG, Cat 3 0.190 (4.8) 101 225
TWISTED PAIR 4-pair, 24 AWG, Cat 5e 0.210 (5.3) 83 184
4-pair, 24 AWG, Cat 6 0.250 (6.3) 58 130
4-pair, 24 AWG, Cat 6a* 0.354 (9.0) 29 65
25-pair, 24 AWG 0.410 (10.4) 21 48
COAXIAL RG6/U 0.270 (6.9) 50 111
FIBER ZipCord 0.118 x 0.236 (3 x 6) 103 230
Round 4 Strand Fiber 0.187 (4.8) 104 233
Round 6 Strand Fiber 0.256 (6.5) 55 124
6000 SERIES RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS
NUMBER OF CONDUCTORS (40% FILL)
WITHOUT WITH DUPLEX WITH SURGE/ LARGE SINGLE
DEVICES RECT. DEVICES GFCI DEVICES RECEPTACLES
WIRE SIZE O.D. 1.59in.
2
(1025mm
2
) 2.30in.
2
(1485mm
2
) 3.00in.
2
(1935mm
2
)
THHN/THWN Inches (mm) Undivided Divided Undivided Divided Undivided Divided Undivided Divided
14 AWG 0.111 (2.8) 659 296 528 231 470 202 412 173
12 AWG 0.130 (3.3) 481 216 395 168 342 147 300 126
10 AWG 0.164 (4.2) 303 136 243 106 216 92 189 79
8 AWG 0.216 (5.5) 174 78 140 61 124 53 109 45
6 AWG 0.254 (6.5) 126 56 101 44 89 38 78 33
4 AWG 0.324 (8.2) 77 34 0 0 0 0 0 0
3 AWG 0.352 (8.9) 65 29 0 0 0 0 0 0
2 AWG 0.384 (9.8) 55 24 0 0 0 0 0 0
1 AWG 0.446 (11.3) 40 18 0 0 0 0 0 0
1/0 AWG 0.496 (12.3) 34 15 0 0 0 0 0 0
2/0 AWG 0.532 (13.5) 28 12 0 0 0 0 0 0
* Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
6000 SERIES RACEWAY WIRE FILL CAPACITIES FOR POWER