Chimney 
The Klassic must be installed using a Class A UL 103 HT approved factory-built chimney system or a 
code-approved masonry chimney with a flue liner. In Canada, the installation must conform to NFPA 211 
or CAN/CSA-B365. The chimney must extend through the roof at least 3’ (1 m), and 2’ (6 m) above any 
structure within 10’ (3 m). The condition of the chimney and height is very important. We recommend a 
minimum height of 10’ (3 m) above the stove collar. However, additional chimney height may be required 
to maintain adequate draft - consult you dealer. 
Note! Mount the special collar using the included hardware. When installing the first piece of pipe (at the 
stove), place the pipe inside the collar, that is designed so any moisture or creosote will drip back into the 
stove and burn away. Install the remaining stovepipe segments with the crimped end down whenever 
possible. 
Required Installation Components 
A. Chimney cap 
B. Insulated chimney 
C. Storm collar 
D. Roof flashing 
E. Ceiling support box or joist shield / firestop 
spacer 
F. Chimney connector pipe 
Chimney connector 
Aluminum and galvanized steel pipe is not 
acceptable for use with the wood stoves. These 
materials cannot withstand the extreme 
temperatures of a wood fire and can give off 
toxic fumes when heated. Do not use connector 
pipe to go through a wall or ceiling. 
Each chimney connector or chimney connector 
section must be installed to the stove flue collar 
and to each other with the male (crimped) end 
toward the stove. 
        A 
       B 
  C 
    D 
        B 
        E 
       F 