WT-9001 IP65 G GS SM MR Re em mo otte eC Co on nttrro oll A An nd d A Alla arrm mS Sy ysstte em m User Manual & Setting Instructions W W T U R A C O R P O R A T O N S D N B H D WIIIT TU UR RA AC CO OR RP PO OR RA AT TIIIO ON NS SD DN NB BH HD D
WT-9001 IP65 GSM Remote Control And Alarm System WT-9001 IP65 GSM REMOTE CONTROL AND ALARM SYSTEM WIRING DIAGRAM DESCRIPTION WT-9001 IP65 – USER MANUAL – Rev. 3.4 – Technical Support: technical@witura.
WT-9001 IP65 GSM Remote Control And Alarm System Example of Trigger Input Connections Example of Controlling Output Connections WT-9001 IP65 – USER MANUAL – Rev. 3.4 – Technical Support: technical@witura.
WT-9001 IP65 GSM Remote Control And Alarm System PACKAGE CONTENTS 1) 2) 3) 4) 5) 6) 1 1 1 1 1 1 pc pc pc pc pc pc IP65 Enclosure WT-9001 Main Board with GSM Module mounted Power Adapter Battery Backup GSM Antenna LCD Display for Assisting in Programming CONTENTS 1. Introduction………………………………………………………………………………………………………………5 2. Features………………………………………………………………………………………………………………………5 3. Characteristic……………………………………………………………………………………………………………5 4.
WT-9001 IP65 GSM Remote Control And Alarm System 1. INTRODUCTION WITURA WT-9001 IP65 GSM Remote Control and Alarm System allow you to use your mobile phone to monitor and control your business from any location. Its alarm facilities provide a flexible way to distribute critical alarm information to any number of mobile phone users. More versatile than a pager system. WT-9001 IP65 provides detailed alarm messages, secure alarm acceptance, full alarm reporting and even remote process control.
WT-9001 IP65 GSM Remote Control And Alarm System 3.1 Standalone Operation Housed in the weather and desk proof IP 65 enclosure complete with internal industrial modem, monitoring controller and flexible operating firmware. It is very easy to setup, install and use. 3.2 8 Digital Inputs Most equipment today does provide some form of alerting signal to interface to monitoring devices from reporting of various malfunction or abnormalities.
WT-9001 IP65 GSM Remote Control And Alarm System 3.4 Querying Inputs And Outputs Status Authorized groups can also query the status of an input or output. This is very useful feature to determine the present status of an input or output. The enquirer need not wait for an alarm to happen in order to receive the given I/O status. 3.5 Turning On/ Off Device Remotely Authorized users can send a SMS command to trigger on or off the digital output.
WT-9001 IP65 GSM Remote Control And Alarm System 3.9 Reliable Performance Besides running the necessary program to perform all the required functions, WT-9001 has diagnostic routines running alongside. Being a monitoring device, WT-9001 must have a very high operating reliability and stability. Every section of WT-9001 is monitoring each other. Should the modem fail to perform its required role, the controller will interrogate and restart the modem. 3.
WT-9001 IP65 GSM Remote Control And Alarm System 4.2 Installing the Components: Antenna, LCD, Power Supply & SIM Card Installing the SIM Card Note: Installing the SIM Card. Please be sure the initial 4 digit PIN code of SIM card is disabled. This can be done by placing it in an unlocked Mobile phone and first checking if the SIM requested any PIN code. If this is the case the PIN code can be disabled using the security settings on the phone. The WT-9001 identifies only 3V SIM Card. Proceed as follows 1.
WT-9001 IP65 GSM Remote Control And Alarm System You should install the WT-9001 in a place where there is GSM signal coming from the operator you want to use. Check it with a phone before proceeding with the installation. If you need to install the device in a place with little signal, you may consider using an external antenna that we may supply as an option to be purchased separately with 5m cable. 4.
WT-9001 IP65 GSM Remote Control And Alarm System 5. WT-9001 IP65 PROGRAMMING INSTRUCTIONS (via SMS Only) You can program the WT-9001 via SMS commands using your phone. Any programming command sent by SMS must be in CAPITAL letters. The fields between square brackets are parameters; do NOT enter the square brackets. When you send a command, you will receive the answer for the first time even if your GSM number is not in the administrator list.
WT-9001 IP65 GSM Remote Control And Alarm System OK WT-9001 And then the WT-9001 will reply a message back to you that the administrator number has been added. Example of Returned Message: TEL1=1111222233 Note: Programming the administrator numbers is necessary in order to operate all other functions and to receive text alerts when the relays activated. 5.
WT-9001 IP65 GSM Remote Control And Alarm System *RLY[N]#XXXXX N stands for Output number 1 - 8 XXXXX stands for 5 digits value: The number of seconds Example: To turn on the output relay number 5 for 1 hour, you can send the following text message to the unit. *RLY5#03600 Example of Returned Message: RELAY5=03600 Note: Sending the following SMS Message to unit will switch off the relay *RLY5#00000 5.3.
WT-9001 IP65 GSM Remote Control And Alarm System 5.3.3 Setting the Recipient of Relay Off Alert The unit can generate text alerts to all 20 of the administrator’s Mobile phone numbers when the relay has turned off. To set the administrator to receive this alert, you would send the following commands by SMS message to the unit.
WT-9001 IP65 GSM Remote Control And Alarm System To turn on input number 1, you can send the following text message to the unit. *CTR1#1 Sending the following SMS Message to unit would mean input 1 will be turned off *CTR1#0 The 1 indicates the ON command and the 0 (zero) indicates the OFF command 5.4.
WT-9001 IP65 GSM Remote Control And Alarm System 5.4.3 Editing the Input Alert Message For (When Input gets High Pulse) The Input Alert Message can be edited and programmed up to 100 characters long. You can change the displayed text by sending the following commands by SMS message to the unit. Note: Only support normal abc/ABC English text, no special characters.
WT-9001 IP65 GSM Remote Control And Alarm System Text Command: *COA[N]#XXXXX N stands for number 1 - 8 of Input XXXXX stands for 5 digits value: The number of times Example: Assume that you want it to send a counter alert message each time the input 1 has triggered for 5 times, you would send the following SMS message to the unit. *COA1#00005 5.4.
WT-9001 IP65 GSM Remote Control And Alarm System Function 3: Function as pulse counter Activate the output relay number (according to which input number applied) to stay on Sends a programmable input alert message (*STR[N]#) once input triggered Generates an alert message once alarm counter reached the alert value Audible alarm will sound once alarm counter reached the alert value (if the alarm function is turned on (*ALM[N]#1)) Function 4: Function as pulse counter Activate the
WT-9001 IP65 GSM Remote Control And Alarm System Function 8: Function as pulse counter Generates a programmable input alert message (*STR[N]#) once input triggered Generates a programmable input alert message (*STO[N]#) once input returned to normal Audible alarm will sound when input return to normal Function 9: Function as pulse counter Switch off output relay 1 Function 10: Function as pulse counter Switch off output relay 2 Function 11: Function as pulse counter S
WT-9001 IP65 GSM Remote Control And Alarm System Note: It is required to reset the Counter Alert Value (*CLA#) each time you change the input function. For more details please refer to page 24 5.5 ALARM SETTINGS 5.5.1 Turning the Audible Siren Functions On/Off When Inputs Triggered The system has the function to sound the connected audible siren when input triggered. This output is available on the connection PIN3 and ground on the main board.
WT-9001 IP65 GSM Remote Control And Alarm System Text Command: *ALAC#X X stands for ON (1) or OFF (0) value When ever the *ALAC#1 command is activated and the power down alarm is on any of the Administrators programmed to receive text alerts, will receive the following messages from the unit in the event of power down and also when power is restored. Power down and text alert received: ACP-OFF Power restored and text alert received: ACP-ON 5.5.
WT-9001 IP65 GSM Remote Control And Alarm System been switched. To activate and also deactivate this function, you can send the following SMS command to the unit. Text Command: *ANTH#X X stands for ON (1) or OFF (0) value When *ANTH#1 is applied, means it will alert the owner by sending a warning message when the SIM Card has been changed. When *ANTH#0 (Default) is applied, means this function is turned off. Alert message received: WARNING! SIM Card Has Been Changed On WT-9001 5.5.
WT-9001 IP65 GSM Remote Control And Alarm System 5.6 MISCELLANEOUS SETTINGS 5.6.1 Inquire All Programmed Administrator Numbers To check all the administrator number in the list, simply send the following SMS command. Text Command: *ADM?# 5.6.2 Inquire the Status of Inputs To check input status, you can send the following SMS command. Text Command: *CTR?# 5.6.3 Reading Counter Alert Value Of Inputs It is possible read all the counter alert value of inputs by sending the following SMS command to the unit.
WT-9001 IP65 GSM Remote Control And Alarm System Text Command: *COU?# 5.6.6 Reading the Sub Increment Counter Value To read the sub increment counter value, you can send the following SMS message to the unit. Text Command: *COT?# Note: The sub increment counter value will be reset automatically each time the alarm counter reached the alert value. 5.6.7 Reset the Total Increment Counter Value To reset the total counter value, you can send the following SMS message to the unit.
WT-9001 IP65 GSM Remote Control And Alarm System To check the signal strength (0-31), you would send the following SMS command to the unit. Text Command: *CSQ?# 5.6.10 Checking the System is Operating Correctly It is possible to check the system is operating correctly by sending the following SMS command to the unit. Text Command: *TEST# When the unit replies TEST-OK indicate the unit is operating correctly. Note: If you receive no reply then unit is not working 5.6.
WT-9001 IP65 GSM Remote Control And Alarm System XXXXXX stands for 6 digits password based on *PAWO# (Default: 123456) and it can be changed anytime. 5.6.13 Reset the WT-9001 (Method 2) To reset the unit using this method, you will need to give a pulse at the input 1 by supplying a DC 12 – 40V and turn on the unit.
WT-9001 IP65 GSM Remote Control And Alarm System REST-D Wait… REST-D OK The unit is reset successfully. 5.6.14 Setting the Function of Opening & Closing time for Output Relay The system has the function to activate the relay for a specific time and then be deactivated for a specific time in a repeating process. To set the opening & closing time of the relays, you can send the following SMS command to the unit. Note: This function only applied in input function 5 and 6.
WT-9001 IP65 GSM Remote Control And Alarm System The WT-9001 can continuously monitor the system status of its own. When there is a problem with system operation or the module is not working properly, it will restart the system automatically to avoid the unit stopped working permanently. If the system failed to respond within 15 – 30 seconds, it will restart the system. 5.6.
WT-9001 IP65 GSM Remote Control And Alarm System 5.6.17 Checking the Software and Hardware Version of WT-9001 To check the software and hardware version of WT-9001, you would send the following SMS command to the unit. Text Command: *EDI?# Example of Returned Message: Software release time:2009/6/02/01:40HW:1.8SW1.0MW1.0 5.7 CONNECTING THE WT-9001 TO THE PC FOR PROGRAMMING The WT-9001 can be program with the provided programmer software.
WT-9001 IP65 GSM Remote Control And Alarm System For software programming details please refer to the WT-9001 Programmer Guide. 6. TECHNICAL SPECIFICATIONS Item Description Model WT-9001 Operating Voltage 15VDC, 2W No of Inputs 8 Digital protected Inputs No of Outputs 8 Relay Outputs - 1A/250 ACV, 1A/48 DCV Communication Port GSM Modem Quad Band 850/900/ 1800/ 1900mhz Humidity Less Than 80% RH Operating Temperature 0°C to 55°C Physical size 225 x 186 x 70 mm Weight 1.
WT-9001 IP65 GSM Remote Control And Alarm System Repeat SMS of alarms User configurable I/O Interface 3.8mm pitch pluggable screw terminal block Remote event log Yes Output pulse capability Yes Display Dot-Matrix LCD with back light, 16 characters x 2 line WARRANTY Witura Corporation Sdn Bhd guarantees all WT-9001 IP65 GSM Remote Control And Alarm System against defective parts and workmanship for 1-year warranty.