Inc GAS COOK TOPS INSTALLATION INSTRUCTIONS

11
Dimensions in parentheses are in
millimeters unless otherwise specified.
INSTALLATION INSTRUCTIONS
CONTACT
I
NFORMATION
Copies of the
standards listed
may be obtained
from:
*National Fire
Protection
Association
Batterymarch Park
Quincy,
Massachusetts
02269
**Canadian
Standard
Association
178 Rexdale Blvd.
Etobicoke
(Toronto), Ontario
M9W 1R3
GAS SUPPLY REQUIREMENTS
LINE PRESSURE TESTING
T
esting above
1
/2 p
si (3.5 kPa) 14" (34.9 mb)
WC (gauge):
The cooktop and its individual
shut-off valve must be disconnected from
t
he gas supply piping system during any
pressure testing of that system at test pres-
sures greater than
1
/2 psi (3.5 kPa).
Testing below
1
/2 psi (3.5 kPa) 14" (34.9 mb)
WC (gauge) or lower:
The cooktop must be
isolated from the gas supply piping system
by closing its individual manual shut-off
valve during any pressure testing of the gas
supply piping system at test pressures
equal to or less than
1
/2 psi (3.5 kPa).
ELECTRICAL REQUIREMENTS
ELECTRICAL SHOCK HAZARD
Plug into a grounded 3-prong adapter.
Do not remove ground prong.
Do not use an adapter
.
Failure to follow these instructions can
result in electric shock, fire or death.
A 120 VAC, 60 Hz, 15-amp, fused electrical
supply is required. A time-delay fuse or circuit
b
reaker is recommended. It is recommended
that a separate circuit serving only this appli-
ance be provided.
Electronic ignition systems operate within
w
ide voltage limits, but proper ground and
polarity are necessary. In addition to checking
that the outlet provides 120 V AC power and is
correctly grounded, the outlet must be checked
by a qualified electrician to see if it is wired
with correct polarity. A wiring diagram is
provided in the literature package.
This appliance, when installed, must be electri-
cally grounded in accordance with local codes
or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70 latest
edition or Canadian Electrical Code (CSA).
RECOMMENDED GROUND METHOD
IMPORTANT NOTE:
For your personal safety,
this cooktop must be grounded. This cooktop
is equipped with a 3-prong ground plug. To
minimize possible shock hazard, the cord must
be plugged into a mating 3-prong ground-type
outlet, grounded in conformance with the
National Electrical Code, ANSI/NFPA 70 latest
edition*, or Canadian Electrical Code (CSA)**
and all local codes and ordinances. If a mating
outlet is not available, it is the obligation of
the customer to have a properly grounded,
3-prong outlet installed by a qualified electri-
cian.
IMPORT
ANT NOTE:
If product is connected to
a GFCI protected outlet, nuisance tripping of
power supply may occur, resulting in loss of
pr
oduct operation.
WIRING DIAGRAM
A wiring diagram covering the control circuit
for each Wolf gas cooktop model can be found
on page 15.
IMPORTANT NOTE:
If codes permit and a
separate ground wire is used, it is recom-
mended that a qualified electrician determine
that the gr
ound path is adequate.
IMPORTANT NOTE:
Check with a qualified
electrician if you ar
e not sure whether the
cooktop is properly gr
ounded.
IMPORTANT NOTE:
Do not ground to a gas
pipe.