Specifications

Dimensions in parentheses are in
millimeters unless otherwise specified.
87
Dimensions in parentheses are in
millimeters unless otherwise specified.
WOLF VENTILATION RECOMMENDATIONS
HVAC
Blower configurations
are for reference
only. Please refer to
minimum CFM recom-
mendations for your
specific cooktop or
module. Always
consult a qualified
HVAC Engineer for
specific applications.
PRO VENTILATION CFM RECOMMENDATIONS
Pro Wall Hoods
Low-Profile W302210I
W362210(I)
W422210 W482210
DF304 / R304 600 600
DF366 / R366 / RT366 900 900
DF364 / R364 / RT364 900 900
RT362 900 900
DF484 / R484 / RT484 900
R482 / RT482 900
NOTE: Do not use Pro low-profile wall hoods with Wolf dual fuel range, gas range or gas rangetop models with a
charbroiler or griddle.
24" (610) Deep W302418 W362418 W422418 W482418 W542418 W602418 W662418
DF304 / R304 600 600
DF366 / R366 / RT366 900 900
DF364 / R364 / RT364 900 900
RT362 900 900
R488 / RT488 1100 1100
DF486 / R486 / RT486 1100 1100
DF484 / R484 / RT484 1100 1100
R482 / RT482 1100 1100
DF606 / R606 1500 1500
DF604 / R604 1500 1500
NOTE: Pro 24" (610) deep wall hoods are not recommended for use with Wolf dual fuel range, gas range or gas
rangetop models with a charbroiler or griddle.
27" (686) Deep W302718 W362718 W422718 W482718 W542718 W602718 W662718
DF304 / R304 600 600
DF366 / R366 / RT366 900 900
DF364 / R364 / RT364 900 900
RT362 900 900
R488 / RT488 1100 1100
DF486 / R486 / RT486 1100 1100
DF484 / R484 / RT484 1100 1100
R482 / RT482 1100 1100
DF606 / R606 1500 1500
DF604 / R604 1500 1500
Model numbers for dual fuel ranges, gas ranges and rangetops indicate width and number of surface burners.
Features such as a charbroiler, griddle and/or French Top will vary.
CFM recommendations are based on total Btu/hr output. Wolf recommends 1 CFM per 100 Btu/hr (.03 kW).
Additional CFM may be required for long duct runs.