Design Guide

wolfappliance.com
|
69
GAS SUPPLY
Installation must conform with all applicable gas codes.
A gas supply line of
3
/4" (19) rigid pipe must be provided
to the gas module. If local codes permit, a certied, 3'
(.9 m)
long,
1
/2" (13) or
3
/4" (19) ID exible metal appliance con-
nector is recommended to connect the units
1
/2" NPT
female inlet to the gas supply line.
When multiple gas cooktops or modules are installed side
by side, they can receive their gas supply from a common
line. However, each unit must have its own regulator
installed between the mainline and the cooktop or module.
Wolf natural gas modules will function up to 10,250'
(3124 m)
in altitude without adjustment and LP gas modules will
function up to 8,600'
(2621 m). If the installation exceeds
these elevations, contact an authorized Wolf dealer for a
high altitude conversion kit.
GAS REQUIREMENTS
NATURAL GAS WC
Supply Pressure 5" (12.5 mb)
Min Line Pressure 7" (17.5 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
LP GAS WC
Supply Pressure 10" (25 mb)
Min Line Pressure 11" (27.4 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
WOLF INTEGRATED MODULES
OVENS / WARMING DRAWERS COOKTOPS / COFFEE SYSTEMS RANGES / RANGETOPS OUTDOOR GRILLS VENTILATION
Planning Information
Refer to the illustrations on the following pages for installa-
tion of integrated modules. For additional induction, electric
and gas modules, refer to the previous cooktop sections.
ELECTRICAL
Installation must comply with all applicable electrical codes.
Locate the electrical supply as shown in the illustrations on
the following pages. A separate circuit, servicing only this
appliance is required.
When multiple cooktops or modules are installed side by
side, each must have its own separate electrical supply.
ELECTRICAL REQUIREMENTS
ELECTRIC MODULES
Electrical Supply grounded 3-wire, 240/208 VAC, 60 Hz
Steamer, Fryer 15 amp dedicated circuit
Induction, Electric, Grill 20 amp dedicated circuit
Conduit exible 4'
(1.2 m)
GAS MODULES
Electrical Supply grounded, 120 VAC, 60 Hz
Service 15 amp dedicated circuit
Receptacle 3-prong grounding-type
Power Cord 6'
(1.8 m)
DRAIN OUTLET
Steamer and fryer modules require a method for draining
hot water and oil. For the steamer module, options include
connecting a drain hose from the
5
/8" (16) outlet tied into
an existing drain, a separate drain with freefall or placing a
heat-resistant receptacle under the drain outlet. For the fryer
module, the drain outlet must be accessible to drain oil into
heat-resistant receptacle.