Design Guide

84 | Wolf Customer Care 800.222.7820
Planning Information
GAS SUPPLY
Installation must comply with all applicable gas codes.
If local codes permit, a certified, 3'
(.9 m) long, ⁄" (13) or ⁄"
(19) ID flexible metal appliance connector is recommended.
When multiple gas cooktops or modules are installed side
by side, they can receive their gas supply from a common
line. However, each unit must have its own regulator
installed between the mainline and the cooktop or module.
Wolf natural gas cooktops will function up to 10,250'
(3124 m) in altitude without adjustment and LP gas cook-
tops will function up to 8,600'
(2621 m). If the installation
exceeds these elevations, contact an authorized Wolf
dealer for a high altitude conversion kit.
GAS REQUIREMENTS
Gas Supply ⁄" ID line
Gas Inlet ⁄" NPT male
NATURAL GAS WC
Supply Pressure 5" (12.5 mb)
Min Line Pressure 7" (17.5 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
LP GAS WC
Supply Pressure 10" (25 mb)
Min Line Pressure 11" (27.4 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
Module Cooktops
GAS REQUIREMENTS
Gas Supply ⁄" ID line
Gas Inlet ⁄" NPT male
NATURAL GAS WC
Supply Pressure 5" (12.5 mb)
Min Line Pressure 7" (17.5 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
LP GAS WC
Supply Pressure 10" (25 mb)
Min Line Pressure 11" (27.4 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)