Design Guide

106 | Wolf Customer Care 800.222.7820
Planning Information
When installing against a combustible surface, a minimum
10"
(254) riser is required for a 36" dual fuel range with
charbroiler or griddle and all 48" and 60" models. Follow all
minimum clearances to combustible surfaces shown in the
illustration on the following page.
A Wolf pro ventilation hood is recommended with the dual
fuel range. Refer to page 150 for Pro Ventilation.
ELECTRICAL REQUIREMENTS
Installation must comply with all applicable electrical codes.
Locate the electrical supply flush with the wall or floor and
within the shaded area shown in the illustration on the fol-
lowing page. A separate circuit servicing only this appliance
is required.
If a power supply cord is being used with models that
require a 50 amp breaker, the cord must be designated for
use with ranges and rated for 240/208, 50 amps and must
include 3 or 4 conductors. A 4-conductor cord is required
for installations where grounding through the neutral is
prohibited.
Wolf dual fuel ranges have a terminal block that allows for
a 3-wire or 4-wire installation.
ELECTRICAL REQUIREMENTS
SINGLE OVEN RANGE
Electrical Supply grounded, 240/208 VAC, 60 Hz
Service 30 amp dedicated circuit
Total Amps 21
DOUBLE OVEN RANGE
Electrical Supply grounded, 240/208 VAC, 60 Hz
Service 50 amp dedicated circuit
Total Amps 42.5
GAS SUPPLY
Installation must comply with all applicable gas codes.
If local codes permit, a certified, 3'
(.9 m) long, ⁄" (13) or ⁄"
(19) ID flexible metal appliance connector is recommended.
Wolf natural gas ranges will function up to 10,250'
(3124 m)
in altitude without adjustment and LP gas ranges will func-
tion up to 8,600'
(2621 m). If the installation exceeds these
elevations, contact an authorized Wolf dealer for a high
altitude conversion kit.
GAS REQUIREMENTS
Gas Supply ⁄" ID line
Gas Inlet ⁄" NPT female
NATURAL GAS WC
Supply Pressure 5" (12.5 mb)
Min Line Pressure 7" (17.5 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
LP GAS WC
Supply Pressure 10" (25 mb)
Min Line Pressure 11" (27.4 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)