Planning Information
GAS SUPPLY
A gas supply line of
3
/4" (19) rigid pipe must be provided
to the gas module. If local codes permit, a certied, 3'
(.9 m)
long,
1
/2" (13) or
3
/4" (19) ID exible metal appliance con-
nector is recommended to connect the units
1
/2" NPT
female inlet to the gas supply line.
When multiple gas cooktops or modules are installed side
by side, they can receive their gas supply from a common
line. However, each unit must have its own regulator
installed between the mainline and the cooktop or module.
Wolf natural gas modules will function up to 10,250'
(3124 m)
in altitude without adjustment and LP gas modules will
function up to 8,600'
(2621 m). If the installation exceeds
these elevations, contact an authorized Wolf dealer for a
high altitude conversion kit.
WOLF INTEGRATED MODULES
GAS REQUIREMENTS
NATURAL GAS WC
Supply Pressure 5" (12.5 mb)
Min Line Pressure 7" (17.5 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)
LP GAS WC
Supply Pressure 10" (25 mb)
Min Line Pressure 11" (27.4 mb)
Max Regulator Pressure 14" (34.9 mb), .5 psi (3.5 kPa)