Operating instructions

Questions? Call Wood Stone at 800-988-8103
4
RFG-IR-W Oven Installation and Operation Manual
October 2007
IF THIS OVEN IS NOT PROPERLY INSTALLED A FIRE MAY RESULT. TO
REDUCE THE RISK OF FIRE, FOLLOW THESE INSTALLATION
INSTRUCTIONS. A MAJOR CAUSE OF OVEN RELATED FIRES IS
FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO
COMBUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT THIS
OVEN BE INSTALLED ONLY IN ACCORDANCE WITH THESE
INSTRUCTIONS.
WARNING: Installation and servicing of this product could expose you
to glasswool/ceramic fibers as well as Calcium Silicate dust. ALWAYS
WEAR RESPIRATORY AND EYE PROTECTION WHEN INSTALLING OR
SERVICING THIS APPLIANCE.
Please read this entire manual before you install the oven. Failure to
follow instructions may result in property damage, bodily injury or even
death. Contact your local building or fire officials about restrictions
and installation inspection in your area.
CLEARANCES
a. The Wood Stone RFG-W oven should have a minimum 1'ā€™
clearance to combustibles from all sides, and 14" clearance to
combustibles from the top (See Figures 1a and 1b on page 6). If
building a facade that will contact the oven, use completely non-
combustible materials*. Please note that standard dry-wall (or sheet
rock) is considered a combustible.
b. Any facade above and/or 6 inches to either side of the oven
doorway, must be constructed of non-combustible building materials.
NOTICE: FOR STUCCO COVERED OVENS (MODEL NUMBERS
ENDING IN ā€œSā€), 36ā€ CLEARANCE TO COMBUSTIBLE BUILDING
MATERIALS IS REQUIRED
*
When non-combustible building materials contact the body of the oven, the
clearances to combustibles are transferred to those non-combustibles.
INSTALLATION CLEARANCES
c. Install this oven only on non-combustible floors. The non-
combustible floor surface should extend 36 inches out in front of the
oven, and extend 30 inches to either side of the oven doorway.