OVEN VENTING
FIRE SUPPRESSION
Check with your local code officials to see if fire suppression is required in your area� If fire suppression is required, you
must vent the oven using a Type 1 hood constructed and installed in accordance with NFPA 96� If fire suppression is
required, Wood Stone recommends providing protection for the hood duct collar and plenum� The fusible link in the hood
must be rated at 450 °F minimum� Wood Stone offers Listed exhaust hoods for our ovens that are pre-piped for ANSUL
R-102 fire suppression� Wood Stone does not recommend aiming any fire suppression nozzles into the cooking chamber
of the oven� All installations are subject to the approval of the local authority having jurisdiction�