VENTING
The following are the manufacturer’s recommendations for venting the Wood Stone MS (Mountain Series) RFG-IR-W
ovens� It is never appropriate to use “B vent” in any part of an exhaust system connected to a Wood Stone oven� All duct
material must be manufactured to the specifications of a grease duct� This is a wood/gas combination oven and must be
vented as a solid fuel piece of equipment� Due to the possibility of sparks entering the system, exhaust systems serving
solid fuel equipment must be vented separately from other non-solid fuel equipment� The duct serving this oven should
be inspected at least twice a month during the first two months of operation, to establish rate of creosote buildup and
necessary cleaning schedule� Typically, we recommend monthly cleaning for all solid fuel ovens� Submit venting plans
to your local authorities before proceeding with your installation, as there may be additional requirements in your area�
There are two venting options�
VENTING OPTION 1
Direct Connection: A Listed building heating appliance chimney, also listed as a grease duct as described in NFPA 96,
connected directly to the oven flue collar and provided with a power ventilator listed for restaurant appliance exhaust�
The power ventilator should be rated for a minimum of 450 °F� Wood Stone does not recommend the use of an in-line
fan� A field built grease duct, constructed and installed to the specifications of a grease duct as detailed in NFPA 96 or
the International Mechanical Code, may also be used�
A static pressure of -0�14 inches water column is necessary at the oven flue collar to ensure that flue gas temperatures
do not exceed 450 °F at the fan inlet� This measurement may be taken by inserting the probe of the magnahelic gauge
through the oven doorway, upwards to the oven flue collar� NOTE: Double door ovens (models ending in “-DD”), have
two flue collars� Both must be connected and a static pressure of negative 0�1 inches must be maintained at each collar�
See table below for CFM required to attain the specified static pressure� NOTE: Solid fuel burning ovens must be vented
separately from non-solid burning equipment�
CFM REQUIREMENTS
Model CFM required
WS-MS-4-RFG-W 425
WS-MS-4-RFG-W 500
WS-MS-4-RFG-W 500
WS-MS-4-RFG-W 550
Install the venting system in accordance with the duct manufacturer’s instructions and in accordance with all local codes�
All field built components should be built to the applicable codes and standards and are subject to the approval of the
authority having jurisdiction�