Instruction manual
500ml
1m
50mm (min.)
PIPEWORK CONNECTIONS
G - Flue manifold condensate outlet
H - Condensate outlet (21.5mmØ) -
supplied
I - Condensate pipe - not supplied
J - Condensate trap
K - Condensate trap fixing bracket -
supplied
CONDENSATE CONNECTION:
4The condensate trap ( J ) must be installed
onto the bracket (K) supplied.
4Measure condens
ate pipe (H) mark and cut
square to length required.
4Fit sealing washer inside condensate pipe
nut and connect to the flue manifold outlet (G).
4Connect 21.5mm polypropylene pipe ( I ) (not
supplied) condensate trap ( J ) before
terminating to waste.
4Ensure that the condensate pipe runs away
from the boiler at a constant fall of 50mm
(min.) for every metre.
4Carefully pour 500ml of water into the
condensate collection (L) to fill condensate trap.
4Check the water is running away and the
condensate pipework joints are water tight.
4Check the flue manifold seal is undamaged
and seated correctly.
4Refit flue manifold access cover (M) and
secure with screws (N).
IMPORTANT: The condensate trap must be
correctly filled to prevent the possibility of
potentially harmful flue products escaping
via the condensate pipework.
IMPORTANT: Insulate all
external condensate pipe
work or run in 32mm pipe
work to prevent freezing.
PIPEWORK CONNECTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR CAMRAY EXTERNAL 12/18-18/25-25/32