Start-up, calibration and operation of the burner
8.7.2 Operations status indication
(*) Without flame signal (with flame during safety time led is
green steady on)
(**) If flame signal detected is greater than 5* flame signal
threshold (3.5 lux), led is green (steady on).
Otherwise number of blinking show flame signal value (n*
3.5 lux).
(***) If the short-circuit socket P is not connected.
8.7.3 Fault diagnostics
Frequency of the flash of reset button for the status indica-
tion
Key
(-) –OFF
G GREEN
O ORANGE
R –RED
Status Reset button color Color code
OFF OFF (-)
Oil pre-heater position GREEN flashing G (-) G (-) G (-) G (-) G (-)
Pre-purge ORANGE blinking O (-) O (-) O (-) O (-) O (-)
Safety time GREEN blinking (*) G (-) G (-) G (-) G (-) G (-)
Running GREEN (**) Steady ON
Shutdown test ORANGE fast blinking O (-) O (-) O (-) O (-) O (-)
Pump priming cycle GREEN, ORANGE, RED G, O, R, G, O, R, G, O, R
Fault description Reset button color Color code
Extraneous light GREEN, RED G, R, G, R, G, R, G, R
Undervoltage or overvoltage RED, ORANGE R, O, R, O, R, O, R, O
Lock-out for no flame during ts RED Steady ON
Lock-out for false flame signal / Lock-out for
burner control error
RED blinking R (-) R (-) R (-) R (-) R (-)
Lock-out for maximum number of repeti-
tions
RED fast blinking R (-) R (-) R (-) R (-) R (-)