Start-up, calibration and operation of the burner
8.7.12 Lock-out types
The control box display causes of malfunctioning any time that
lock-out occure, identified by the reset button color. The se-
quence of led pulses in the reset button issued by the control box
identifies the possible types of malfunction, which are listed in the
table below.
The frequency of the flash of reset button for the status indication,
See “Fault diagnostics” on page 22.
8.7.13 Controlled intermittent operation
After 24 hours of continuous operation at the latest, the control-
box will initiate automatic reset shut-down followed by a restart.
Description Lock-out time Led color Probable cause
The flame is not detected
after the safety time
Immediate RED
Steady ON
flame detector defective or dirty;
oil valve defective or dirty;
faulty ignition transformer;
badly regulated burner;
oil fuel not present.
Presence of extraneous
light the turning on of the
burner
After max. 25 seconds RED
blinking
presence of a extraneous light after the limit thermostat
switching on;
presence of extraneous light during pre-purging.
Flame failure during oper-
ation
After 3 recycles RED
fast blinking
badly adjusted burner;
oil valve defective or dirty;
flame detector defective or dirty.
WARNING
To reset the control box after visual diagnostics
have been displayed, you must press the reset
button.