Instruction manual

27
3266
GB
Faults / Solutions
10.1.1 Operating faults
In digital applications the burner goes in lock-out after 4 flame fail-
ure (for flashing frequency See “Fault diagnostics” on page 22).
Key for reset button color
(-) –OFF
R –RED
Fault Possible cause
Digital
fault
diagnostics
Solution
The burner goes into
lockout mode during
operation.
Flame failure. R,(-),R,(-)
Fast blinking
Clean or replace the flame detector.
Replace the dirty or deteriorated nozzle.
Check the efficiency of the flame detector.
Check the efficiency of the piston on the pressure
adjuster.
Check the efficiency of the pump cut off valve.
WARNING
The manufacturer cannot accept responsibility for
any damage to persons, animals or property due
to error in installation or in the burner adjustment,
or due to improper or unreasonable use or non
observance of the technical instruction enclosed
with the burner, or due to the intervention of un-
qualified personnel.