Instruction manual
MAINS SUPPLY
ELECTRICAL SUPPLY:
• Supply: 230V - 50Hz.
• Cable: PVC insulated 0.75mm
2
(24 x
0.2mm) temperature rated to 90°C.
• Protection IP45.
• External 5A fuse to BS 1362.
• The appliance must be earthed.
• Please refer to IEE regulations for cross
bonding requirements.
• It must be possible to isolate the appliance
from the electric supply with at least a 3mm
contact separation in both poles supplying
the appliance.
• Wiring between the appliance and the
electrical supply must comply with IEE wiring
regulations and any local regulations which
may apply for fixed wiring to a stationary
appliance.
• Any system connected to the boiler must not
have a separate electrical supply.
IMPORTANT: The appliance provides a permanent external electrical supply
for servicing and must therefore be fed via a circuit breaker incorporating
earth leakage protection.