INSTRUCTION MANUAL INSTALLATION COMMISSIONING & SERVICING FLOOR STANDING RSF GAS-FIRED CONDENSING COMBINATION BOILER GREENSTAR HIGHFLOW 440CDi & 550CDi FOR SEALED CENTRAL HEATING SYSTEMS AND MAINS FED DOMESTIC HOT WATER THE APPLIANCE IS FOR USE WITH NATURAL GAS OR L.P.G.
CONTACT INFORMATION WORCESTER, BOSCH GROUP: RECEPTION: 0844 892 9900 MAIN FAX: 01905 754619 TECHNICAL: 0844 892 3366 SERVICE: 0844 892 3000 SPARES: 01905 752571 LITERATURE: 0844 892 9800 TRAINING: 01905 752526 SALES: 01905 752640 WEBSITE: worcester-bosch.co.uk INSTALLATION & SERVICING INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION.
SAFETY & REGULATIONS CONTENTS SAFETY & REGULATIONS SAFETY PRECAUTIONS 2 INSTALLATION REGULATIONS 2 GENERAL INFORMATION 3 TECHNICAL DATA 4 LAYOUT & COMPONENTS 5 APPLIANCE INFORMATION APPLIANCE INFORMATION PRE-INSTALLATION 6 MAINS SUPPLIES 7 WATER SYSTEMS & PIPEWORK 9 CONDENSATE PIPEWORK 11 PRESSURE RELIEF PIPEWORK 12 BOILER LOCATION & CLEARANCES 13 MOUNTING FRAME CONNECTIONS 14 TERMINAL OUTLET POSITIONS 17 ROOM SEALED FLUE OPTIONS 18 PREINSTALLATION CLEANING PRIMARY SYSTEMS 19
SAFETY & REGULATIONS SAFETY PRECAUTIONS INSTALLATION REGULATIONS IF YOU SMELL GAS: Failure to install appliances correctly could lead to prosecution. DO NOT SMOKE OR STRIKE MATCHES. DO NOT TURN ELECTRICAL SWITCHES ON OR OFF.
GENERAL INFORMATION STANDARD PACKAGE: A - Floor standing gas fired combination boiler for central heating and domestic hot water. C - Literature pack. D - Condensate waste pipe & non-return valve A SPECIFICATIONS: APPLIANCE INFORMATION B - Mounting frame complete with preplumbing manifold assembly. Pre-wired and pre-plumbed. Galvanised steel inner frame. Bosch Heatronic control system. Automatic ignition. 850mm Direct burner ignition electrodes. Built-in frost thermostat.
TECHNICAL DATA DESCRIPTION UNITS Natural Gas L.P.G 440CDi 550CDi 440CDi 550CDi APPLIANCE INFORMATION Central Heating Max. rated heat output net 40/30°C kW 31.2 32.8 31.2 32.8 Max. rated heat output net 50/30°C kW 30.9 32.5 30.9 32.5 30.6 Max. rated heat output net 80/60°C kW 29.2 30.6 29.2 Max. rated heat input net kW 29.6 31 29.6 31 Min. rated heat output net 40/30°C kW 8.4 11 11.6 13.4 Min. rated heat output net 50/30°C kW 8.3 10.9 11.4 13.2 Min.
LAYOUT & COMPONENTS The diagram opposite shows the controls in the servicing position and excludes the outer case, inner covers and wiring.
CLEANING PRIMARY SYSTEMS IMPORTANT: All the following pre-installation sections must be read and requirements met before starting boiler or flue installation. CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS. IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty.
MAINS SUPPLIES ELECTRICAL SUPPLY: • Supply: 230V - 50Hz. • Cable: PVC insulated 0.75mm2 (24 x 0.2mm) temperature rated to 90°C. • External 3A fuse to BS1362. • The appliance must be earthed. • Wiring between the appliance and the electrical supply must comply with IEE wiring regulations and any local regulations which may apply for fixed wiring to a stationary appliance. • Any system connected to the boiler must not have a separate electricity supply.
MAINS SUPPLIES GAS SUPPLY: • Boilers using NG must be connected to a governed meter. • LPG boilers must be connected to a regulator. • Installation and connection of the gas supply to the boiler must be in accordance with BS6891. • Under no circumstances should the diameter of the gas supply pipe be less than that of the appliance inlet connection.
WATER SYSTEMS & PIPEWORK PRIMARY SYSTEM PLASTIC PIPEWORK: • Any plastic pipework must have a polymeric barrier with 600mm (minimum) length of copper connected to the boiler. • Plastic pipework used for underfloor heating must be correctly controlled with a thermostatic blending valve limiting the temperature of the circuits to approx. 50°C. The pipework from the boiler to the blending valve must be in copper.
WATER SYSTEMS & PIPEWORK FILLING PRIMARY SYSTEMS: Water main supply Heating return Hose return Stop cock Temporary hose Non return valve Non return valve Test cock • The CH sealed system must be filled using a WRAS approved filling loop or comply with the diagram opposite for system fill. • The filling point must be at low level and must never be a permanent direct fixing to the mains water supply.
CONDENSATE PIPEWORK IMPORTANT: Visible air break at plug hole • Ensure there are no blockages in the pipe run 100mm siting a soak-away to avoid obstructing existing services Insulation or increase pipe size 22mmØ plastic pipe • Condensate waste must not Open end of condensate drainage pipe directly into gully below grating but above water level 75 mm min.
PRESSURE RELIEF PIPEWORK IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty. • The pressure relief drain pipe (A) should be at least 15mm diameter copper pipe and run downwards away from the boiler and discharge away from any electrics or other hazard, preferably to an external drain or soakaway.
BOILER LOCATION & CLEARANCES • This boiler is only suitable for installing internally within a property at a suitable location onto a fixed rigid non-combustible surface at least the same size as the boiler and capable of supporting the boiler weight. 1: INSTALLATION CLEARANCES 1200mm 610mm 600mm • THIS BOILER IS NOT SUITABLE FOR ROOF SPACE INSTALLATION.
BOILER LOCATION & CLEARANCES 4: AIRING CUPBOARD CLEARANCES 625mm 800mm 4: AIRING CUPBOARD CLEARANCES: Diagram 'd' opposite shows the minimum space required to install and service the boiler within an airing cupboard. 5: VENTING COMPARTMENTS: 1050mm 25mm PREINSTALLATION 5: VENTING COMPARTMENTS If the clearances are less than those stated for options '3' & '4' (above) then ventilation must be provided as described in BS 5440.
MOUNTING FRAME CONNECTIONS CONNECTIONS: Water: 22mm compression fittings Gas: 22mm compression fitting. PRE-PLUMBING: • With the mounting frame (A) installed, pipework can be connected to the valves on the plumbing manifold. • The system can be filled (without the boiler being connected) using an optional charging link assembly (B). • The boiler can be installed at a later date.
TERMINAL OUTLET POSITIONS All measurements in millimetres 300 6 Dormer Window 500 25 5 7 14 400 8 10 PREINSTALLATION 25 1,500 Velux Window 9 11 200 Drainpipe 300 25 4 3 500 600 500 300 1,200 12 13 1,500 300 2 Boundary Window 300 15 600 1 300 NOTE: All measurements are the minimum clearances required. Terminals must be positioned so to avoid combustion products entering the building. Key to illustration 1. Flue clearance must be at least 300mm from the ground.
PLUME MANAGEMENT KIT POSITIONS All measurements in millimetres Plume management deflector: 180° Flue Exhaust Outlet Air Intake 8 PREINSTALLATION 7 3 200 300 200 2 1,200 Balcony 4 150 200 600 1 200 25 300 150 Window 300 Window 300 200 5 Window Door Boundary 25 150 150 150 6 Drainpipe NOTE: All measurements are the minimum clearances required. Terminals must be positioned so to avoid combustion products entering the building. Key to illustration 1.
ROOM SEALED FLUE OPTIONS L= Ø100mm 140 - 530mm L= Ø125mm 350 - 1200mm L= Ø125mm 9000mm The diagrams (opposite) show the components used and the maximum flue length for each configuration of Ø100mm and Ø125mm flues. L L A Min. 120mm A B Ø125mm x8 C • Only straight flue sections can be reduced in length by cutting. • The Ø100mm horizontal flue terminal can be fitted from inside or outside the building.
IMPORTANT: All the previous Pre-Installation sections must be read and requirements met before starting boiler or flue installation. UNPACKING THE BOILER Take care not to damage the boiler panels or the floor and note that the boiler may contain some water due to factory testing. Unpacking: 2 1 1 Undo the ties securing the carton to the pallet If a sharp implement is used, care must be taken not to pierce the carton or cause injury.
All dimensions in mm F D D A B MOUNTING FRAME FIXING & FLUE OPENING CAUTION: Ensure there are no pipes, electric cables, damp proof course or other hazards before drilling. B SAFETY: 112 65 98.5 65 65 81 20 All relevant safety precautions must be undertaken. Protective clothing, footwear, gloves and safety goggles must be worn as appropriate. MOUNTING FRAME/PIPEWORK POSITIONS: A - Mounting frame. B - Manifold connections. C - Mounting frame fixing point. 38mm D - Wall.
MOUNTING FRAME CONNECTIONS CAUTION: ISOLATE THE MAINS GAS SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS. GAS AND WATER CONNECTIONS: Ensure all pipework is clean and each pipe is in the correct position as shown opposite. Push in each pipe in turn and tighten the fitting to secure. A - CH flow (22mm) B - DHW flow (22mm) C - Gas inlet (22mm) D - Mains water inlet (22mm) E - CH return (22mm) INSTALLATION F - Mounting frame.
FLUE LENGTHS HORIZONTAL FLUE: 1 (60/100mm diameter) L For vertical flues and 80/125mmØ horizontal flues, please refer to separate Flue manuals. Ø60/100mm HORIZONTAL TELESCOPIC FLUE LENGTHS: The maximum effective straight flue lengths (L) are stated opposite for the relevant appliance and must not be exceeded.
FLUE MEASURING & CUTTING 1 Flue bends: 1 950mm 1145mm Connecting flue bends increases the effective pipe length and an allowance must be made for the different connectors. The example opposite shows dimensions for two 90° bends connected to a standard flue extension. Adjusting the standard terminal length: 2 2 530mm Extend tube (A) by withdrawing from tube (B) to achieve the flue length required, 310- 530mm. Secure with screw provided and seal joint with the aluminium tape supplied.
FLUE MEASURING & CUTTING FLUE OUTLETS (L or P): P L 1 2 L 3 Remove seal (B) from flue adaptor (A). Cut square to mark, as shown, deburr and clean. Replace seal (B). 2 L INSTALLATION 1 A B 3 2 P 1 A B 3 B 24 FLUE MEASURING & CUTTING INSTALLATION & SERVICING INSTRUCTIONS 8 716 115 219c (03.
FLUE INSTALLATION D 1 2 Remove retaining screw (A) to swing control panel assembly (B) outwards to its full extent. Remove screws (C) from inside of casing. Lift front of top panel (D) to release. Pull forwards to disengage rear retainer (E), then lift panel (D) away from boiler. 3 H E 4 C Pull clip (F) outwards to release the expansion vessel(G). Swing expansion vessel (G) outwards.
STANDARD FLUE INSTALLATION 1 NOTE: to ease assembly of the flue components, grease seals lightly with the solvent-free grease supplied. B Check all the seals are seated properly in the grooves provided and are in good condition. All flue joints must be sealed to prevent leakage of condensate and flue products. Installing the standard flue: 2 1 Set the flue terminal (B) to the distance required, secure with screw and seal joint with the aluminium tape supplied.
2m EXTENDED FLUE INSTALLATION 1m 52mm NOTE: to ease assembly of the flue components, grease seals lightly with the solvent-free grease supplied. 104mm Check all the seals are seated properly in the grooves provided and are in good condition. TOP D B C All flue joints must be sealed to prevent leakage of condensate and flue products.
FLUE TERMINAL PLUME MANAGEMENT The flue discharge can be redirected allowing some plume management control, alternatively, a complete plume management system can be fitted to the flue terminal. 2 A Redirecting the flue discharge: Important: should you wish to use the plume deflector please use the additional grease enclosed to ensure that an adequate seal is retained. 1 1 Remove screws (A) and terminal end (B).
CONDENSATE, GAS & WATER CONNECTIONS CONDENSATE CONNECTION: H The condensate pump (G) fills up and periodically discharges through the flexible condensate pipe (H) between 200mm to 4500mm from floor level. After this point the condensate flows, due to gravity, down the 21.5mm plastic pipe to the outlet. Max. 4500mm Fit the bayonet connector on the end of the condensate waste pipe to the condensate pump. Push down and rotate clockwise until the connector is locked.
PRESSURE RELIEF VALVE OUTLET A B Fitting the pressure relief valve drain pipe: Connect a length of 15mm copper pipe (A) to the P.R.V drain pipe (B). C The P.R.V drain pipe (B) should be at least 15mm diameter and run down away from any electrics or other hazard. IMPORTANT: The pressure relief valve is a safety device for the boiler and if activated may discharge boiling water or steam through the P.R.V drain pipe. Auto air vent: INSTALLATION Remove the auto air vent cap (C) and discard.
ELECTRICAL 1 CAUTION: ISOLATE THE MAINS ELECTRICITY SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS 2 NOTE: The mains electrical supply to the boiler and system wiring centre must be common and through either a common fused double pole isolator or a fused three pin plug and unswitched socket. A B The isolator shall be situated next to the boiler for new systems and, where practicable, replacement boilers.
PRE-COMMISIONING CHECKS CAUTION: ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS. 2 1 Check that the service and water pipes are connected to the correct valve on the manifold; A - CH flow (22mm) B - DHW flow (22mm) C - Gas inlet (22mm) D - Mains water inlet (22mm) 3 E - CH return (22mm) 2 Check the gas type specified on the identification plate matches that of the gas supply.
FILLING THE SYSTEM 1 2 3 Turn on the water main and open the system valves (align slot vertically). Open all radiator valves. Unscrew the tank drain cap and connect the integral filling loop between the Flow valve and the Tank drain valve. Open the flow and tank drain valves. Fill the system to a pressure up to 2 bar. Close the flow valve. 4 Vent all radiators, retighten the vent when completed. Check the system and correct any leaks. 5 The boiler integral expansion vessel is pre-charged to 0.
WATER TREATMENT IMPORTANT: Debris from the system can damage the boiler and reduce efficiency. Failure to comply with the guidelines for the use of water treatment with the appliance will invalidate the appliance warranty. FLUSHING (Central Heating): Switch off the boiler. Open vented systems only: turn off the water to the system header tank. Open all radiator valves/drain cocks and drain the system while the appliance is hot. Close drain cocks.
K A I D E F H L M STARTING THE APPLIANCE IMPORTANT: Never run the appliance when the appliance or system is empty or unpressurised. Switching the appliance on/off: 1 Turn on mains power supply. Turn on any external controls. Set the TRV controls to maximum. C Set the clock/programmer to continuously ON and the room thermostat to maximum temperature. G B J A - MASTER SWITCH FOR ON/OFF 2 Press button (A) and the power on indicator (B) illuminates blue.
FINISHING COMMISSIONING A NOTE: At the time of commissioning, complete all relevant sections of the Benchmark Checklist located on the inside back pages of this document. 1 B 1 Engage top panel (A) onto rear retainers (B) and lower front of panel into position. Secure with screws (C). 2 C Swing control panel assembly (D) into the boiler. Secure with screw (E). 3 2 D Locate bottom corners of the front panel (F) into retainers (G). Push top of door to engage clips.
CAUTION: TURN OFF THE GAS SUPPLY AND ISOLATE THE MAINS SUPPLIES BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY IMPORTANT: AFTER REPLACEMENT OF ANY COMPONENTS ALWAYS CHECK FOR GAS TIGHTNESS WHERE RELEVANT AND CARRY OUT FUNCTIONAL CHECKS AS DESCRIBED IN COMMISSIONING. ANY O-RING OR GASKET THAT APPEARS DAMAGED MUST BE REPLACED. INSPECTION & SERVICE IMPORTANT: Any service work must be carried out by competent registered engineers, such as British Gas or other GAS SAFE registered personnel.
INSPECTION & SERVICE SERVICE INSPECTION: J 1 Grip the outer sides of the front panel (A) pull and lift away from retaining lugs (B). 2 Remove retaining screw (C) to swing control panel assembly (D) outwards to its full extent. 3 Pull clip (E) outwards to release expansion vessel (F). G D H C 4 2 Swing expansion vessel (F) outwards. Note: for easier access to the inner case, the expansion vessel can be unhooked (by removing the retaining screw on the hinge) lowered and moved to the side.
IMPORTANT: AFTER COMPLETING THE APPLIANCE SERVICE THE CO/CO2 MUST BE CHECKED AND SET TO THE LIMITS IN THE SECTION “AIR/GAS RATIO”. INSPECTION & SERVICE If the Heat Exchanger requires cleaning: An accessory kit is available (No. 840) specifically designed for cleaning the heat exchanger. If required order 7 719 001 996. 2 Remove the cleaning access cover (B), seal (C) and metal plate (D) securing it, if present. 3 Unscrew the condensation trap cap and place a suitable container underneath.
INSPECTION AND SERVICE Burner: NOTE: On re-assembly, replace the seal Check that the boiler is completely isolated from the gas supply. C 1 A Remove the clips (A) and unscrew the castellated nuts (B). Remove springs. Unscrew and remove the two hexagon screws (C) securing the fan. D Slacken fully the rear securing bolt (D). E F B D G Remove the burner cover plate (E). 2 Remove the burner (F) and clean the components. Do not use a wire brush. Re-assemble burner in reverse order using a new seal (G).
CAUTION: TURN OFF THE GAS SUPPLY AND ISOLATE THE MAINS ELECTRICAL SUPPLY BEFORE STARTING ANY WORK AND OBSERVE ALL RELEVANT SAFETY PRECAUTIONS. DRAIN THE BOILER/SYSTEM WHERE NECESSARY AND PROTECT ANY ELECTRICS FROM WATER INGRESS DURING COMPONENT REPLACEMENT. IMPORTANT: Refit or replace any components removed from the appliance in the reverse order using new gaskets/'O' rings/sealant/heat transfer paste where necessary. Any 'O' ring or gasket that appears damaged must be replaced.
NOTE: A SERVICE TO THE FAN ASSEMBLY AND FLAP VALVE MUST NOT BE ATTEMPTED IF A CO/CO2 ANALYSER IS NOT AVAILABLE. REPLACEMENT PARTS Fan Assembly: Undo lower pipe union on gas pipe (E). Remove fan lead and earth connector. The earth connector has a positive clip fixing. A B Remove fixing screws attaching fan (A) to the burner cover (B). Remove fan (A) with gas pipe (E) and mixer unit (D). Twist mixer unit (D) with gas pipe (E) to separate from fan (A).
REPLACEMENT PARTS Sensors: Check that the appliance is electrically isolated. Central heating flow temperature sensor (A): Remove the connector. Release the sensor clip and withdraw the sensor. A Apply heat transfer paste to the replacement sensor. B Drain the system first: Safety temperature limiter (B): Remove the connectors. Unscrew the sensor. Tank sensor (C): Remove screws retaining plastic cover. Remove cover and disconnect 2 electrical connections. Unscrew 2 hexagon studs.
REPLACEMENT PARTS Domestic hot water heat exchanger: Before removing the heat exchanger, close the inlet valves, drain the hot water circuits and tank. A The pipe (A) may be removed between the flow sensor outlet and the plate heat exchanger to improve access to the rear connections. Undo the two screws securing the plastic housing to the heat exchanger. Remove the heat exchanger. To refit, follow the above in reverse. Ensure any seals that have been disturbed are replaced.
REPLACEMENT PARTS Electrode assembly: Switch off the master switch. Isolate appliance from the power supply. Move control panel into service position. Release 4 screws to remove inner case door. Remove the leads from the electrodes. Unscrew the two fixing screws (B) and carefully remove the electrode assembly (A). Replace and re-connect the assembly taking care not to mislay the inspection window. D E C F After re-assembly check CO/CO2 levels as described in the section “Setting the air/gas ratio”.
SETTING THE AIR/GAS RATIO 1 IMPORTANT: The appliance is set at the factory and adjustment to the CO2 settings (air/gas ratio) is only required where the appliance has been stripped down and assembled or if the fan, burner or gas valve are replaced or the appliance has been converted to a different gas type. A The air/gas ratio may only be adjusted on the basis of a CO2 measurement at maximum and minimum heat output using an electronic tester.
SHORT PARTS LIST 1a 2 3 1a Burner skin seal: 1b Part No. 8 711 004 168 0 (GC No. E27 201) 1b Burner: Part No. 8 718 006 658 0 (GC No. E27 200) 2 Fan assembly: 440CDi: Part No. 8 717 204 410 0 (GC No. H66 918) 4 5 6 550CDi: 7 Part No. 8 717 204 453 0 (GC No. H26 536) 3 Circulating Pump assembly: Part No. 8 718 681 477 0 (GC No. H66 929) 4 Diverter valve assembly: Part No. 8 716 106 845 0 (GC No. H02 533) 5 Diverter valve motor: Part No. 8 716 106 847 0 (GC No. H02 534) 6 Flow sensor: Part No.
L.P.G. CONVERSION Change code plug: 1 Release three screws (A) to remove cover (B). 2 Remove and dispose of the existing code plug (C). C Replace with new conversion code plug. 2 N.G. code plug number: 440CDi 1700 550CDi 1702 L.P.G. code plug number: B 440CDi 1701 550CDi 1703 Refit panel (B) and secure with three screws (A). 1 Change gas pipe: A 4 Rotate gas pipe (D) anti-clockwise, pull upwards and remove gas pipe.
ELECTRICAL WIRING DIAGRAM PRE WIRED LINK DIAGNOSTIC INTERFACE CODE PLUG 230V HW interface (Installer Module) ST1 located to the right of the control panel ST18 Fuse F2, T 1.6A, L250V Red Yellow 230V/AC White Fuse F3, T 0.5 A, L250V Pink NO 9V C NC WORCESTER 24V CONTROLS OPTION, PLUG IN POINT (under blanking cover on fascia) ST9 Orange Violet EMS BUS contacts (for FX controls) Blue Red Orange Blue Yellow Green Black ST17 SPARK TRANSFORMER Fuse F1, slow T2.
50 MAI N SWITCH ON GREEN LIG HT ON FAULT FINDING & DIAGRAMS CENTRAL HEATING FUNCTION LOCKOUT Pump ON. Diverter valve to CH position. CE NTRAL H EATI NG DE MAN D YE S Fan to start speed. Gas valve open. 5th Attempt? NO Ignition spark 5 second (max). Burner remans OFF until flow temperature is below set value. Fan run to purge gas from burner. NO BURNER LIT? YE S RED LIG HT ON Burner stabilises at start speed for 5 - 10 seconds. Gas valve shuts. Pump remains ON. CH demand satisfied.
INSTALLATION & SERVICING INSTRUCTIONS 8 716 115 219c (03.2010) GREEN LIG HT ON FAULT FINDING & DIAGRAMS MAI N SWITCH ON Ignition sequence. Tank demand (overrides central heating demand). Ignition sequence. Pump ON. Diverter valve to Hot Water position. Hot water demand (overrides all other demands). Gas valve OFF until temperature drops to set level. Minimum heat imput until 50°C if boiler unused for long period.
FAULT FINDING BOILER - FAULTS AND CONDITIONS NOTE ; This fault finding information is for guidance only. Worcester Bosch cannot be held responsible for costs incurred by persons not deemed to be competent. Display code: Fault description Check, repair/replace as necessary A5 Tank NTC defect Check tank NTC sensor and leads, measure resistance across NTC (33.5kΩ- 500Ω) A7 DHW NTC defect Check DHW NTC sensor and leads, measure resistance across NTC (33.
GAS BOILER COMMISSIONING CHECKLIST This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference. Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing controls.
Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW Tel. 0844 892 9900 Fax. 01905 754619 Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd. worcester-bosch.co.uk 8 716 115 219c (03.