Technical data

SERVICING AND SPARES
6 720 648 547 (2012/06)42
13. ELECTRODE ASSEMBLY
Disconnect spark electrodes and flame sensor connection.
Remove two screws (F).
Remove spark/flame electrode assembly (G) from heat exchanger.
Inspect the spark/flame electrode assembly and ceramics for signs of
contamination or damage, replace as necessary.
If necessary, clean the spark/flame electrode assembly with a plastic
scouring pad.
Replace electrode gasket.
Re-assemble with the new gasket and secure with the screws (F)
removed earlier.
Fig. 66 Electrode assembly
14. AIR/GAS MANIFOLD
1. Remove cover panel (A) by removing screws (B).
Check that the boiler is completely isolated from the gas supply.
Fig. 67 Top panel
2. Remove clips (C) and unscrew the two bolts (D).
Unscrew and remove the two hexagon screws (E) securing the fan.
Slacken fully the rear securing bolt (F).
Fig. 68 Release air/gas manifold
3. Remove air/gas manifold (I)
Fig. 69 Air/gas manifold
4. Open air/gas manifold (I).
Carefully withdraw diaphragm (J) from fan intake tube and check for
soiling and splits.
Fig. 70 Diaphragm
WARNING: Electrode gasket
Do not remove the electrode assembly unless a new
gasket is available for re-assembly.
WARNING: Air/Gas manifold
Do not remove the manifold unless a new gasket is
available for re-assembly.
13
G
F
6720647361-38.1Wo
AB
6720647361-63.1Wo
B
1.
F
C
D
2.
6720647361-64.1Wo
H
G
EE
3.
6720647361-65.1Wo
J
I
K
I
4.
6720647361-66.1Wo