Instruction manual

PRE -
INSTALLATION
FLUE OPTIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 12i/24i System
8 716 115 167b (03/2009)
17
The Greenstar series has the option of two horizontal RSF (60/100 telescopic and
80/125) flue systems and two vertical RSF (60/100 or 80/125) flue systems:
The systems have different maximum flue lengths
This page shows various fluing options with the straight flue lengths required to achieve
the maximum flue length. Note that:
each 90° bend used is equivalent to 2 metres of straight flue
each 45° bend used is equivalent to 1 metre of straight flue
NOTE: Plume management kits are available for the 60/100 horizontal flue option.
Refer to the manual supplied with the Plume management kits for complete
installation instructions
Telescopic horizontal flue assembly
Horizontal flue extension
High level horizontal flue
Horizontal flue with 2x90° bends
High level horizontal flue with 2x90° bends
High level horizontal flue with 3x90° bends
Vertical balanced flue assembly
Vertical balanced flue system with 2x45° bends
Vertical balanced flue with 2x90° bends
FLUE OPTIONS
Maximum total flue length
100mmØ 125mmØ
12 i system 4,600mm 13,000mm
24 i system 4,600mm 13,000mm
Maximum total flue length
100mmØ 125mmØ
12 i system 4,600mm 13,000mm
24 i system 4,600mm 13,000mm
Maximum total flue length
100mmØ 125mmØ
12 i system 2,600mm 11,000mm
24 i system 2,600mm 11,000mm
Maximum total flue length
100mmØ 125mmØ
12 i system 2,600mm 11,000mm
24 i system 2,600mm 11,000mm
Maximum total flue length
100mm‚Ø 125mmØ
12 i system N/A 9,000mm
24 i system N/A 9,000mm
Maximum total flue length
100mmØ 125mmØ
12 i system 6,400mm 15,000mm
24 i system 6,400mm 15,000mm
Maximum total flue length
100mm‚Ø 125mmØ
12 i system 4,400mm 13,000mm
18 i system 4,400mm 13,000mm
Maximum total flue length
100mmØ 125mmØ
12 i system 2,400mm 11,000mm
24 i system 2,400mm 11,000mm
Maximum telescopic flue length
100mmØ 125mmØ
12 i system 570mm 1,070mm
24 i system 570mm 1070mm