The Greenstar gas-fired condensing wall mounted regular boiler series Technical and specification information 1
Worcester, Bosch Group Technical Help line Worcester and you. Making a difference.
The Greenstar condensing regular boiler range The Greenstar regular range is part of a market leading Hence, SEDBUK Band A ratings for all models in the range of energy-saving condensing wall mounted Greenstar condensing range. The Greenstar regular range at a glance Output kW to central heating (CH) 12Ri 15Ri 18Ri 24Ri 30CDi Regular 40CDi Regular Min 4kW 5kW 6kW 8kW 7.7kW 9.4kW Max 12kW 15kW 18kW 24kW 30kW 40.
The features of the Greenstar condensing regular boiler range A condensing boiler is more efficient due to its ability to Fluing options extract more heat from the flue gases normally lost to the The Greenstar regular range features 2 different sizes of environment through the flue system. multi-directional RSF flue systems, 100mm or 125mm.
Greenstar Ri regular technical data Inside story – Greenstar Ri condensing regular boiler series Model 21 20 19 22 1 Greenstar 12Ri Greenstar 15Ri Greenstar 18Ri Greenstar 24Ri Height (mm) 600 600 600 600 Width (mm) 390 390 390 390 Depth (mm) 270 270 270 270 Weight – dry (kg) 22.6 22.6 22.6 22.6 SEDBUK value % / band – natural gas 90.1% / Band A 90.1% / Band A 90.1% / Band A 90.2% / Band A SEDBUK value % / band – LPG 91.4% / Band A 91.4% / Band A 91.4% / Band A 92.
Inside story – Greenstar CDi Regular condensing boiler series Greenstar CDi Regular technical data Model Greenstar 30CDi Regular Greenstar 40CDi Regular Height (mm) 760 (max) 760 (max) Width (mm) 440 440 Depth (mm) 360 (max) 360 (max) 39.5 39.5 SEDBUK value % / band – natural gas 90.3% / Band A 90.2% / Band A SEDBUK value % / band – LPG 92.3% / Band A 92.
Installing the Greenstar regular range Compartment installation Wall preparation The appliance may be installed in any room, although The following diagrams show the wall mounting jigs which particular attention is drawn to the requirements of the enable a simple and straightforward method of attaching the boiler to the wall surface.
Pipework connections and casing dimensions Boiler location & clearances Bathrooms (When fitted to wall frame) Depth to wall C IMPORTANT: Any switch or appliance control using mains electricity must A boiler with a mechanical timer or RF mechanical timer not be within reach of a person using the bath or shower. with a room thermostat must only installed outside the shaded area. Electrical switches, fused spurs and socket outlets must not be situated in the bathroom.
Condensate pipe work Internal condensate pipe work • Where a new or replacement boiler is being installed, access to an internal “gravity discharge” point should be one of the factors considered in determining boiler plastic pipe Condensate drainage pipe can be run above or below ground.
Plume management terminal positioning External condensate pipe work Insulate & increase pipe size 100mm dia. ±45° Plume management deflector: External rain water pipe into foul water Syphon trap External air break Air gap Flue exhaust outlet 8 Drainage holes Syphon trap 180° Air intake 12mm dia. 300mm 500mm min. Pipe work transition All measurements in millimetres 100mm dia. min.
Flue terminal positioning All measurements in millimetres 300 6 Dormer window 7 500 25 5 14 25 1,500 Velux window 400 8 10 9 11 200 Drainpipe 300 1,200 25 4 3 500 600 300 12 13 1,500 500 300 2 Boundary Window 300 15 600 1 300 Note • All measurements are the minimum clearances required. • Terminals must be positioned so to avoid combustion products Key to illustration 1. entering the building.
Greenstar regular boiler range horizontal fluing options The Greenstar regular boiler range have the choice of Option 1 Option 3 Standard horizontal flue assembly Extension flue horizontal using a second 90º bend Accessories 2 differently sized horizontal RSF flue systems, a 100mm diameter telescopic flue kit including a plume management Components kit and a 125mm diameter telescopic flue kit. Both systems Part no. 7 716 191 082 100mm dia.
Option 5 Option 6 Extension flue upwards and horizontal Extension flue upwards and horizontal using a second 90º bend using a third 90º bend Greenstar regular boiler range vertical fluing options The Greenstar regular boiler range have the choice of Accessories 2 differently sized vertical RSF flue systems, 100mm and 125mm. Both systems have different maximum lengths. Components Part no. Options 1 to 4 detail the permissible lengths.
Option 2 Option 4 Vertical balanced flue system maximum height Vertical balanced flue system with two 90º bends Pitc roo hed f Greenstar regular boiler range plume management system options 500mm Flat roof 300mm Standard plume management system Plume management system The flue terminal outlet has built-in stops to limit rotation 60mm dia. plume management kit for horizontal fluing to allow condensate to run back into Comprises: the boiler for safe disposal.
Condensfit II telescopic flue and plume management Greenstar Ri regular boilers are able to use the maximum system measuring 100mm dia. internal flue length of 4,600mm regardless of the amount of plume management selected. Fig A Option 1 Option 3 Plume management system Plume management system with extensions and 45º bend External plume management bends still need to be allowed for. See below. 500mm (min) (M) L (max) For Greenstar CDi Regular boilers the 100mm dia.
Option 5 Plume management system with extensions and 45º bends Installation requirements Installation of the Greenstar regular boiler range must be in The following is a list of major items which must be fitted accordance with the relevant requirements of the Gas to the system: Safety (Installation Use) Regulations (as amended), current IEE Wiring Regulations, local Building Regulations, Building 1. Safety valve – 3bar Standards (Scotland) regulations and bylaws of the local 2.
Open vented primary systems Natural gas supply Liquid Petroleum Gas (LPG) supply The Greenstar regular boiler range is designed for For the Greenstar Ri series when on a full output The Greenstar Ri regular appliance is available in an LPG connection to an open vented fully pumped heating and demand will require up to 3.02m3/hr of gas (depending version. The appliance, when on demand at full output will hot water system. on the model). require 0.5m3/h, 0.96Kg/h, (17.7ft3/hr) for the 12Ri, 0.
Greenstar regular boiler range accessories 34 RS telescopic flue kit (100mm dia.) Long telescopic flue kit (100mm dia.) Standard telescopic horizontal flue kit (125mm dia.) Vertical BF kit (100mm dia.) Support bracket kit (100mm dia.) Support bracket kit 6 pack (100mm dia.) Support bracket kit (125mm dia.) Below boiler pipe cover Worcester Part No. 7 716 191 082 Worcester Part No. 7 716 191 171 Worcester Part No. 7 719 003 702 Worcester Part No. 7 719 002 430 Worcester Part No.
The very best training programmes from Worcester Worcester training courses One stop shop training OFTEC ASSESSMENT We are here to provide you with training and assistance for OFTEC 101 Covering Domestic/Light Commercial Pressure Jet Commissioning and Servicing and Sales & Marketing are just 2 of the courses we now offer Duration 3 day course has established close partnerships with many colleges to help your business grow.