Failure identification procedure
d3 flashing.
Wrong signal from pin 8-9 (open?).
Check Action
1. B Turn ON the appliance.
B Measure voltage between Termi-
nal 4 and Terminal 8.
Voltage 24 V DC?
yes: 2.
no: 3.
2. Existing heat store thermostat con-
nected to Terminals 7, 8 and 9?
yes: B Power OFF the appliance.
B Fix the additional bridge 8-9 in the right position
and close the screws.
B Turn ON the appliance.
d3? 3.
no: 4.
3. Break in connecting lead? yes: B Power OFF the appliance.
B Plug the connection wire.
B Turn ON the appliance.
d3? 4.
no: 4.
4. The PCB control board is damaged. B Make a note of the altered service settings (see
table 1, "First Service Level; Values that can be
modified" at page 8 and table 5, "Secondary
Service Level; Values that can be modified" at
page 11).
B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change PCB control board.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
B Restore service settings previously noted down.