Failure identification procedure
5. Natural gas models:
does the building have a supply pres-
sure regulator?
yes: B Check that it is fitted correctly and functioning
properly and correct if necessary.
B Check supply pressure, inform gas company if
outside correct range.
B Is correct code plug fitted?
B Press , restart the appliance.
EA? 6.
no: 6.
LPG models:
is the flow rate of the gas supply to
the appliance correct?
yes: 6.
no: B Is there enough gas in the supply cylinder?
B Is there air in the supply pipe?
B Is the solenoid valve in the "meter cabinet” open-
ing?
B Is the supply pressure OK? (if the supply pres-
sure is too high, check the pressure regulator in
the “meter cabinet” and on the LPG supply cylin-
der).
B Press , restart the appliance.
EA? 6.
6. Is the ground connection correct? yes: 7.
no: B Correct the electrical ground connection.
B Press , restart the appliance.
EA? 7.
7. Two phase net:
Is there a resistor fitted between Pe
and N?
yes: 8.
no: B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Insert a 2 M resistance between the ground
and the N connection.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
B Press , restart the appliance.
EA? 11.
EA and flashing.
No flame ionisations signal
Check Action