Failure identification procedure
13.
B Press buttons and simulta-
neously.
B Select service-function 5.1.
Continuous ignition (without gas)
OK?
yes:
B Press buttons and simultaneously.
14.
no:
B Press buttons and simultaneously.
17.
14. Ignition lead connected to ignition
electrodes?
yes: 15.
no: B Connect cable to ignition electrode.
B Press , restart the appliance.
EA? 15.
15. Ignition cable connector engaged in
switchbox?
yes: 16.
no: B Power OFF the appliance.
B Engage ignition cable connector in switchbox.
B Turn ON the appliance.
B Press , restart the appliance.
EA? 16.
16. Is the ignition electrical wire
damaged?
yes: B Power OFF the appliance.
B Change the ignition electrical wire.
B Turn ON the appliance.
B Press , restart the appliance.
EA? 17.
no: 17.
17.
B Press button .
B Select service-function 3.3.
Is the ionisation quality 2. or 3. ?
yes: 19.
no: 18.
18. Electrode assembly defective?
B Power OFF the appliance.
B Remove electrode assembly.
Electrodes worn out?
yes: B Replace electrode assembly.
B Turn ON the appliance.
B Press , restart the appliance.
EA? 19.
no: B Refit electrode assembly.
B Turn ON the appliance.
B Press , restart the appliance.
EA? 19.
EA and flashing.
No flame ionisations signal
Check Action