Specifications

7 181 465 346 GB (03.02)
20
Failure identification procedure
AC flashing.
Module not detected.
(Constant CH flow temperature according to CH temperature control on boiler.)
Check Action
B Note the setting of the temperature controls
and .
1.
B Press button .
B Select service function 1.9 .
Code 0., 2., 4., 5. is displayed.
yes: No modul detected.
B Disconnect connecting lead between PCB con-
trol board and TA 211 E or TA 212 E.
B Re-connect connecting lead.
AC? 3.
no: 2.
2. Are 24 V DC cables routed along-
side 230 V AC cables?
yes: B Ensure cable separation conforms to minimum
requirements as per installation instructions and/
or use shielded cable.
no: 3.
3. Connecting lead between PCB con-
trol board and TA 211 E or TA 212 E
defective.
B Power OFF the appliance.
B Replace connecting lead between PCB control
board and programmer interface module or TA
211 E.
B Turn ON the appliance.
AC? 4.
4. TA 211 E connected? yes: 5.
no: 8.
5. B Select service function 1.6 .
Outside temperature between -20
and +30 ˚C is displayed.
Does temperature displayed
match true outside temperature?
yes: 7.
no: B Power OFF the appliance.
B Replace outside temperature sensor.
B Turn ON the appliance.
AC? 7.
6. If remote control installed:
B Select service function 1.7 .
Remote control status 0. is dis-
played .
yes: B Power OFF the appliance.
B Plug the connection wire.
B Turn ON the appliance.
AC? 7.
no: 7.