Bosch Heatronic board functions
7
The next time the central heating or heat store calls for
heat, the appliance is held at a low heat output for 15
minutes. The display shows
-II-
in alternation with the
CH flow temperature.The factory setting is
1
(enabled).
To switch off the trap filling programme to carry out
servicing work:
B
Press and hold the and buttons simultane-
ously until the display shows
= =
.
The and buttons will light up.
B
Turn the temperature control until the display
shows
8.5
.
After a short delay, the display then shows the trap
filling programme setting (
1.
= Enabled).
B
Turn the temperature control until the display
shows 0. (= Disabled).
The display and the and buttons will flash.
B Press and hold the and buttons simultane-
ously until the display shows [ ].
The trap filling programme is now disabled.
B Regulate the temperature control and the tem-
perature control on the previously set positions.
The display shows the heating outlet temperature.
Display shows
0
0
(venting function)
The first time the appliance is switched on, it automati-
cally activates a one-off venting sequence in which the
heating pump switches on and off at intervals for about
8 minutes.
This function can be activated on Service Level 2, Serv-
ice Code 7.3, if it is required at any other time.
If the condensation trap is not filled with
water, flue gas can escape!
B The trap filling programme should only
be disabled in order to carry out servic-
ing work.
B Always re-enable the trap filling pro-
gramme after completing servicing
work.