Instructions

EN
54
3.
5. You can correct the end point in small steps by briefly pressing the set button (11).
IMPORTANT
In the event that a malfunction occurs during configuration, e.g. in the event that the tubular motor only runs for a single rotation even when
the Set button is pressed, it is unlikely that the tubular motor is faulty. Possibly the adapter (10) has slipped off of the motor head.
Check and, if necessary, correct the positioning of the adapter (10), see pages 41 and 56.
NOTE
The end points are maintained permanently even in the event of power failure.
Press and hold the corresponding set button (11) until the desired end point is reached.
The roller shutters travel up or down.
Release the set button (11) as soon as the roller shutters have reached the desired position.
The motor stops and the first end point is stored.
Switch on the mains power.1.
Manual setting of upper / lower endpoint with help of the
set button on the tubular motor
4.
Repeat points 2 to 4 for the second end point.
IMPORTANT
If the “external switch (h) lead is not used, then it must be connected to the neutral conductor (f) (see fig. n).
6.
ON
Check the configuration and allow the roller shutters to run in both
directions, until the end points switch off the motor.
Thermal protection
The tubular motors are designed for brief operation (approx. 4 mins).
If this period is exceeded, or if the equipment is switched over frequently, then the motor
may heat up and the thermal protection system will shut it off.
In this case, allow the motor to cool down for 20 minutes.
Modifying the end points
Move the roller shutters back to the centre position and begin the process again.
Test run / modifying the end points
or
SET
or
2. Move the roller shutters in the desired direction of travel. In doing so, observe the switching sequence.
The switching sequence for the SET button or the external switch is: OPEN/STOP/CLOSE/STOP, and so on.
If the tubular motor is already logged on to the DuoFern network, then the direction of travel can also be specified with DuoFern transmitters.
Manually setting the upper / lower endpoints with DuoFern transmitters
NOTE
The end points can also be set with a DuoFern manual transmitters or with the DuoFern
central operating unit.
In order to do so, please read the operating instructions for the corresponding DuoFern
transmitter.
Persons can be injured or property damaged if end points are configured
using DuoFern transmitters without a direct line of sight to the roller
shutters.
Watch the moving roller shutters and keep other people away from the area until
the movement has completed.
Symbols and actions when connecting a cord circuit setting unit (22)
or
when connecting an external switch.