TReX User Manual v2.14 Firmware
This is the ID of the remote device that all inputs will be sent to. When the MODE is
configured to be SCADA_MASTER this is the ID of the first SCADA_SLAVE TReX. All
SCADA_SLAVES must be consecutively numbered following this ID.
When the MODE SCADA_SLAVE is used, the REMOTE_ID is configured to be the same as
the LOCAL_ID (this is required by the SCADA_MASTER to identify the source of the
transmission).
REMOTES
This parameter is only used when the MODE is SCADA_MASTER. This is the number of
wireless SCADA_SLAVE units that the SCADA_MASTER will communicate with.
INPUTS
This is a shortcut to the INPUT configuration menu.
OUTPUTS
This is a shortcut to the OUTPUT configuration menu. If the OUTPUT is DISABLED, then
messages from a remote unit can NOT change the units outputs. This may be desired if the
OUTPUT is already configured for another purpose such as LINK FAIL OUTPUT. Outputs to
be used should be set to LATCHED.
REFRESH TIME
How long in seconds before sending all input information again. If any INPUT changes then
there is an immediate transmission. The REFRESH TIME ensures that if a message is lost, the
remote device will eventually resynchronise its OUTPUTS with the local device INPUTS.
DELTA ADC TX
Analog data is transmitted after each REFRESH TIME count elapses. This field allows an
immediate transmission if it has changed by a certain amount since its last transmission. This
is the raw ADC count that is a value up to 1023. Min value is 10 to ensure that very small
changes do not result in continuous transmissions in an electrically noisy environment.
SERIAL LINK
Configuration of all SERIAL LINK Settings
MODBUS
Configuration of all MODBUS Settings