Installation Guide

Installation
10 975-0126-02-01
generators to have their neutral conductors tied to ground at the source of power in
the same way that the neutral conductor from the utility is tied to ground. These
same codes specify that the neutral can only be connected to ground in one place
at any one time.
Suitability This automatic neutral-to-ground bonding system is suited for installations in
which the AC input source is known to have a bonded neutral. This will be the
case in most situations: in a utility feed, at an external AC hook-up, or a generator
with a bonded neutral. If not, have an electrician look into bonding the sources
neutral to ground. See also AC Input and Output Isolation on page 20.