TM SW Series Addendum to the Installation and Operators Manual for SW4024, SW4048, SW5548 Models Only ã©2000 2000 Xantrex Technology Inc. #976-0013-01-01 Rev.
©2000 Xantrex Technology Inc.
ADDENDUM The items listed in this addendum have changed to reflect product compliance with UL1741 First Edition requirements. The changes only affect 120 VAC/60 Hz units using the SELL mode function of the inverter/charger. The software revision has changed from 4.01 to 4.10. Model Numbers Affected: SW4024, SW4048 and SW5548 (120 VAC/60 Hz models only) General Information: The inverter software has been redesigned to meet UL1741 First Edition requirements which incorporates IEEE929 recommended practices.
ADDENDUM Changes in Manual: Page-1, 5, 34, 39 and 119All references to software version 4.01 should now read 4.10. Page 1 and 17The SW4024, SW4048 and SW5548 inverter models are UL listed to UL1741-First Edition which incorporates IEEE929 recommended practices.
ADDENDUM Menu Maps The USER and SETUP menu have been updated to reflect the new software revision as follows: Page 34USER MENU. The software revision shown under menu heading TRACE ENGINEERING 3, menu item REVISION 4.01 is changed to REVISION 4.10. An information file has been added to menu heading 11 and reads: IN SELL MODE AC1 INPUT VAC LIMITS FIXED AT 88% AND 110% OF NOMINAL. Menu System Page 39TRACE ENGINEERING (3) menu heading. The software revision has been updated from 4.01 to 4.10.
ADDENDUM Over/Under Voltage Fluctuations VOLTAGE MAXIMUM TRIP TIME* Voltage < 60 V (< 50%) 6 cycles Voltages between 60–106 V (50–88%) 120 cycles Voltages between 106–132 V (88–110%) Normal operation Voltages between 132–165 V (110–137%) 120 cycles Voltage >165 V (137%) 2 cycles FREQUENCY MAXIMUM TRIP TIME* Frequency < 59.3 Hz 6 cycles Frequency > 60.
©2000 Xantrex Technology Inc.
5916 - 195th Street N.E., Arlington, WA 98223 Phone: (360) 435-8826 visit our website at: www.traceengineering.