Troubleshooting
3–8 975-0401-01-01
High Battery voltage
fault (>16.6V)
Discontinue or disconnect AC power source from
supplying power to the charger.
Disconnect voltage sensitive DC loads from DC
supply to prevent damage.
If the DC bus voltage is still measuring high after AC
power has been disconnected, call a qualified and
certified electrician.
High Charger Temp
warning (>50°C)
Check that the battery type and temperature settings
match the actual battery.
Allow the Truecharge™ 2 Battery Charger to cool.
Improve ventilation or install in cooler location. If the
temperature increases, the Truecharge™ 2 Battery
Charger will display a fault and stop functioning.
If the optional remote panel is installed, set a lower
limit on the output current to cool down the charger.
High Charger Temp
fault (>70°C)
Check that the battery type and temperature settings
match the actual battery.
Allow the Truecharge™ 2 Battery Charger to cool
while the AC is connected so the fan stays on.
Improve ventilation or install the charger in cooler
location.
Flashing LED Solid LED
Table 3-1
Interpreting Fault and Warning Indicators
Fault or Warning
Condition
Temp Fan AC Battery Fuse Charger Remote Fault
Solution