Configuring the Freedom SW using the SCP
Charger Settings Menu
The Charger Settings menu provides options for configuring the
Freedom SW to operate from your battery bank.
Figure 25
Ch
ar
g
er
Settings
Menu Screen
FSW3012 00: Chg Settings
Batt Type
Custom Settings
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
Absorb Time
Auto Recharge
Default Batt Temp
[Flooded]
[440Ah]
[100%]
[3-Stage]
[12.5V]
[180min]
[Enabled]
[Warm]
[*Flooded] [Gel] [AGM] [Custom]
[*3-Stage] [2StgNoFloat]
[*Enabled] [Disabled]
[*Warm] [Hot] [Cold]
Follow procedures on “To select and change a
configurable setting:” on page 33 to change the settings.
Table 10
Setting Defaults and Ranges
Model Freedom SW 2012 / 3012 Freedom SW 2024 / 3024
Item Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom
Flooded Flooded, Gel,
AGM, Custom
Batt Capacity
2000-watt models
250Ah 50Ah 2000Ah 250Ah 50Ah 2000Ah
Batt Capacity
3000-watt models
440Ah 440Ah
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
ReCharge Volts 12.5V 11.0V 13.5V 25.0V 22.0V 27.0V
Absorb Time 180min 1min 480min 180min 1min 480min
Auto ReCharge Enabled Enabled,
Disabled
Enabled Enabled,
Disabled
Default Batt
Temp
Warm Hot, Warm, Cold Warm Hot, Warm, Cold
Freedom SW 3K2K InvChg Owners Guide.book Page 48 Wednesday, October 9, 2013 1:34 PM