MS2000 Operation Guide MS2000 Sine Wave Inverter/Charger
MS2000 Sine Wave Inverter/Charger Operation Guide
About Xantrex Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical power.
About This Guide Purpose The MS2000 Sine Wave Inverter/Charger Operation Guide provides explanations and procedures for operating, configuring, and troubleshooting the MS2000 Sine Wave Inverter/Charger (MS2000). Scope The guide provides safety guidelines and information about operating, configuring, and troubleshooting the unit. It does not include installation information or battery information. Refer to the MS2000 Sine Wave Inverter/ Charger Installation Guide.
About This Guide “Warranty and Product Information” contains the product warranty, explains how to return a product for service, and describes what to prepare for a call to Xantrex Customer Service. Conventions Used The following conventions are used in this guide. WARNING Warnings identify conditions or practices that could result in personal injury or loss of life. CAUTION Cautions identify conditions or practices that could result in damage to the unit or other equipment.
About This Guide Related Information For related materials on this product and its available accessories, see also: MS2000 Sine Wave Inverter/Charger Installation Guide (975-0126-02-01) System Control Panel Owner’s Guide (975-0083-01-01) Automatic Generator Start Owner’s Guide (975-0082-01-01) Xanbus System Installation Guide (975-0136-01-01) More information about Xantrex Technology Inc. as well as its products and services, including a complete list of Xanbus-enabled devices, is available at www.xantrex.
vi
Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS The MS2000 Sine Wave Inverter/Charger Operation Guide contains important safety instructions. Before you install and use your MS2000 Sine Wave Inverter/Charger, be sure to read, understand and save these safety instructions and those in the other product guides. Read all instructions and cautionary markings on the inverter/charger, the batteries and all appropriate sections of this guide.
Safety capacitors remain charged after all power is disconnected. For instructions on obtaining service, see the “Warranty and Product Information” section in the MS2000 Sine Wave Inverter/Charger Operation Guide. 7. Do not expose the inverter/charger to rain, snow, or splashing bilge water. 8. To reduce risk of electric shock, disconnect all sources of AC and DC power from the inverter/charger attempting any maintenance or cleaning. Turning off controls will not reduce this risk. 9.
Safety Explosive Gas Precautions WARNING: Risk of explosive gases Working in the vicinity of a lead-acid battery is dangerous. Batteries generate explosive gases during normal battery operation. For this reason, it is of utmost importance that you must read this guide and follow its instructions closely each time before you service equipment in the vicinity of the battery. 1.
Safety 9. If it is necessary to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off, so as not to cause an arc. 10. Be sure area around battery is well ventilated. 11. Clean the battery terminals. Be careful to keep corrosion from coming in contact with your eyes. 12. Study all battery manufacturer’s specific precautions such as removing or not removing cell caps while charging and the recommended rates of charge. 13.
Contents Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - vii 1 Introduction About the MS2000 Sine Wave Inverter/Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 Premium Power and Ease of Use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 How MS2000 Works - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3 Inverting - - -
Contents Charger Operation with Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - -2–17 Operating in Equalization Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–18 Equalizing Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–19 Terminating the Equalization Process - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–22 Operating Limits for Charger Op
Contents Clear Faults - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - View Device Info - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Basic Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Selecting the MS2000 Advanced Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Returning to MS2000 Basic Menu - - - - -
Contents A Specifications Inverter Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Main Charger Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Echo Charger Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Transfer and General Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Environm
Figures Figure 1-1 Figure 1-2 Figure 1-3 Figure 1-4 Figure 1-5 Figure 1-6 Figure 1-7 Figure 2-1 Figure 2-2 Figure 2-3 Figure 2-4 Figure 2-5 Figure 2-6 Figure 2-7 Figure 2-8 Figure 2-9 Figure 2-10 Figure 2-11 Figure 2-12 Figure 2-13 Figure 2-14 Figure 2-15 Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Figure 3-5 Figure 3-6 Figure 3-7 Figure 3-8 Figure 3-9 Figure 3-10 Figure 3-11 Figure 3-12 Figure 3-13 Figure 3-14 Figure A-1 Figure B-1 Typical Xanbus System Diagram - - - - - - - - - - - - - - - - - - - - - -
xvi
1 Introduction Congratulations on your purchase of the MS2000 Sine Wave Inverter/ Charger. The MS2000 has been designed to give you premium power, ease of use, and outstanding reliability. Please read this chapter to familiarize yourself with the main performance and protection features of the MS2000.
Introduction About the MS2000 Sine Wave Inverter/Charger The MS2000 Sine Wave Inverter/Charger is a convenient combination of an inverter, multistage battery charger, transfer switch, and Echo Charger in one electronic device. • • • • As an inverter, the MS2000 provides sine wave power for your microwave, entertainment system, computer, and other loads. This power is identical to the AC source provided from the utility grid (power company).
Introduction How MS2000 Works The MS2000 is designed to: • • invert charge With AC input available from the utility grid or a generator, power is passed through the MS2000 Sine Wave Inverter/Charger to operate connected AC loads. The remaining AC power not used by loads is converted to DC power and used to charge batteries.
Introduction Built-in Charge Formulas For the inverter to perform at the highest level, the batteries must be charged correctly. The MS2000 has optimized algorithms for flooded, gel, and AGM batteries. Battery Temperature Sensor Since battery temperature is a key factor in correct charging, the charging formula must be adjusted (automatically and continuously) according to the actual battery temperature to ensure that batteries are fully charged, but not overcharged.
Introduction Xanbus System Xanbus is a network communications protocol, developed by Xantrex. In a Xanbus® system, the MS2000 is the device that typically provides network power—800 mA at 15 volts DC. All of the Xanbus-enabled devices, such as the MS2000, the System Control Panel (SCP), and the Automatic Generator Start (AGS) are able to communicate their settings and activity to each other. See Figure 1-1.
Introduction Comprehensive Electronic Protection MS2000 is CSA approved to UL 458 (including the Marine Supplement) and CSA C22.2 No. 107.1, and it is designed to American Boat and Yacht Council (ABYC) recommended practices E-11 and A-25 for marine use. See “Regulatory Approvals” on page A–5 for more information. MS2000 is equipped with numerous protection features to ensure safe operation.
Introduction MS2000 Features Front Panel Features Before you begin to operate the MS2000, review the front panel features shown in Figure 1-2 and described in Table 1-1. A detailed view of the lights and buttons on the front panel is shown in Figure 1-3 and described in Table 1-2. 4 2 2 3 2 1 3 2 Figure 1-2 Front Panel of the MS2000 Table 1-1 Front Panel Features Feature Description 1 AC wiring compartment access panel provides access to the terminal block for wiring the AC input and AC output.
Introduction 54 3 2 1 6 7 10 9 8 11 12 13 Figure 1-3 Front Panel Lights and Buttons Table 1-2 Description of Front Panel Lights and Buttons Feature Description 1 External AC light illuminates when you are connected to an AC source like the utility grid or a generator and the AC is qualified. 2 Inverter ON light illuminates when the MS2000 is operating in invert mode. 3 Low Battery light illuminates when the battery voltage is low.
Introduction Side Panel Features CAUTION: Equipment Damage Connect only to other Xanbus compatible devices. Although the cabling and connectors used in this network system are the same as Ethernet connectors, this network is not an Ethernet system. Equipment damage may result from attempting to connect two different systems. The side panel features with all connections completed is shown in Figure 1-4 and Figure 1-5.
Introduction Figure 1-5 DC Grounding Completed 1–10 975-0125-02-01
Introduction DC Terminal Covers and Battery Temperature Sensor DC Terminal Covers Two covers are supplied to prevent accidental contact with the cabling connectors after installation. The red cover is for the positive cabling terminal, and the black cover is for the negative cabling terminal.
Introduction System Accessories and Network Components System accessories can be used with the MS2000 in a Xanbus system. The System Control Panel (SCP) provides configuration and monitoring capability for Xanbus-enabled devices such as the MS2000. Automatic Generator Start (AGS) automatically starts and stops your generator.
2 Operation Chapter 2, “Operation” contains information and procedures for using your MS2000. This chapter begins with a system startup check that you carry out after installation and configuration to verify that the MS2000 is operating correctly. If you’re using the System Control Panel to operate or monitor the status of the unit, also refer to the System Control Panel Owner’s Guide.
Operation Operating the MS2000 with the System Control Panel The System Control Panel (SCP) provides operating, configuration, and monitoring capability for your Xanbus system. The System Control Panel: • • • • • Monitors activity throughout your onboard power system. Displays the latest information about your inverter/charger, battery voltage and current level, battery charge output, and generator start and stop activity. Displays the settings for each Xanbus-enabled device in the system.
Operation Using the System Control Panel Display screen The System Control Panel has important features which you’ll want to be familiar with, as shown in Figure 2-1. System information is shown on the display screen with an adjustable backlight. Indicator lights Four indicator lights on the front panel indicate the operating status of the Xanbus system. Push buttons Four push buttons allow you to select device menus and change or display settings.
Operation Table 2-1 System Control Panel Features and Buttons Feature Description 6 Up arrow button • Scrolls up one line of text. • Increases a selected value. 7 Down arrow button • Scrolls down one line of text. • Decreases a selected value. 8 Exit button • Cancels selection of a menu item. • Returns you to the previous screen. 9 System button: • Toggles all Xanbus-enabled devices on the system between Operate mode and Power Save mode. See “System Modes” on page 2–6.
Operation System Start-up Check WARNING Review the “Important Safety Instructions” on page vii before operating the inverter/charger. To test the charging and inverting functions from the MS2000 front panel: 1. Disconnect AC power from MS2000 AC input by opening the breaker or disconnect. Press the Inverter Enable button on the MS2000. The Inverter On light illuminates. 2. Place a load on the inverter.
Operation System Modes This section provides an overview of the four different system modes. The system modes described in this section affect the performance and behavior of the MS2000 and all other Xanbus-enabled devices on the Xanbus system. You’ll have to change the system mode when putting your boat in storage, or when installing a Xanbus-enabled device. You can change system modes using the System Settings menu on the System Control Panel.
Operation Operate Mode Characteristics In Operate mode, all communications are enabled on the Xanbus system. All power conversion functions are enabled. Each Xanbus-enabled device is monitoring and communicating its input. The basic state of the System Control Panel is Operate mode. In Operate mode, the System Control Panel communicates with other Xanbus-enabled devices and displays all the network information which it is configured to display.
Operation You can also enter or exit Power Save mode on the System Settings menu by selecting Desired Mode and scrolling to PowerSave as shown in Figure 2-4. Operate [Advanced] Figure 2-4 Power Save Mode Returning to Operate mode If an inverter/charger supplies power to the network, applying AC input with utility power or generator power automatically returns the system to Operate mode.
Operation Putting the System into Safe Mode When you are installing or removing devices from the Xanbus system, putting the system into Safe mode prevents unexpected behavior. To enter Safe mode: 1. On the Select Device menu, use the down arrow button to highlight System. The cursor on the right of the screen indicates where you are in the menu. Figure 2-5 Select Device Menu 2. Press Enter. The System Settings menu appears. Figure 2-6 System Settings Menu 3.
Operation Figure 2-7 Safe Mode 5. Press Enter. You are now in Safe mode. 6. Press Exit twice to return to the System Home Screen. To exit Safe mode and return to Operate mode: 1. On the System Settings menu, under Desired Mode, select “Operate.” 2. Press Enter. Hibernate mode Characteristics Hibernate mode removes network power from the System Control Panel and all Xanbus-enabled devices on the Xanbus system.
Operation If an inverter/charger supplies power to the network, you can bring the system out of Hibernate mode either by pressing the reset button on the inverter/charger front panel or by applying AC input with utility power or generator power.
Operation Operating in Invert Mode WARNING Review the “Important Safety Instructions” on page vii before operating the inverter/charger. Once the inverter/charger is installed, you can operate it in invert mode. To operate in invert mode from the front panel: 1. Press the Inverter Enable button on the MS2000. 2. If external AC is present, the External AC light illuminates. If AC is present and you want to run the inverter, remove AC so the inverter turns on.
Operation Operating Limits for Inverter Operation Power Output Temperature The continuous output rating for the MS2000 is 2000 watts or 17 amps at 120 volts AC. The MS2000 can deliver this power in an ambient (surrounding) temperature up to 122 °F (50 °C). Above this temperature, you must reduce the power demand or the unit may shut down to protect itself against overheating.
Operation Operating in Charger Mode WARNING: Explosive Gases Review the “Important Safety Instructions” on page vii before operating the inverter/charger. During charging, batteries may generate explosive gases. Thoroughly ventilate the areas around the batteries and ensure that there are no sources of flames or spark in the vicinity. Study all battery manufacturer’s precautions such as removing or not removing cell caps while charging and the recommended rates of charge.
Operation Echo Charger Operation For the built-in Echo Charger to operate, both the Echo Charger and the main charger must be set to Enabled. By default, the Echo Charger is enabled by the MS2000 to charge an engine battery 10 seconds after the main charger has entered Bulk or Absorption mode, and the house battery voltage is at 13.2 volts DC or higher. The Echo Charger’s maximum charge current is 10 amps.
Operation 3. Use the down arrow button to scroll to Echo Chg. 4. Press Enter. [30A] Max Chg Rate [100%] [Enabled] Figure 2-9 Echo Charger 5. Use either arrow button to highlight Enabled and Disabled. 6. Press Enter. [30A] Max Chg Rate [100%] [Enabled] Figure 2-10 Echo Charger Enabled 7. Press Exit to return to the Select Device menu.
Operation Charger Operation with Battery Temperature Sensor Since battery temperature is a key factor in optimal charging, the house battery charger voltage will be adjusted (automatically and continuously) according to the actual battery temperature to ensure that the house battery is fully charged, but not overcharged.
Operation Operating in Equalization Mode WARNING: Explosive gases Equalization generates explosive gases. Ensure adequate ventilation. CAUTION: Batteries may be damaged Sealed lead-acid batteries and gel batteries must NEVER be equalized or premature battery failure will result. Equalize mode is disabled if you have selected “Gel” and “AGM” as the battery type. Only flooded (wet) lead-acid batteries should be equalized.
Operation Equalizing Batteries Important: Equalization will be carried out after an absorption charge. Equalization only runs for 60 minutes and may need to be restarted if the specific gravity is still uneven. To equalize your batteries: 1. Turn off or disconnect all loads on the battery. The voltage applied to the battery during equalization may damage your electronic equipment. As well, equalization won’t proceed correctly if loads are drawing current from the battery. 2. Check electrolyte level.
Operation Yes No Figure 2-13 Equalize Confirmation Warning Selecting Yes by pressing the Enter button takes you to the equalization system home screen, as shown in Figure 2-14. OR Selecting No by pressing the Exit button on Figure 2-13 takes you to the MS2000 device screen. Yes n/a 13.0V Menu Cancel Figure 2-14 Equalization Home Screen See Table 2-2 for an explanation of the equalize home screen content.
Operation Table 2-2 Equalization Home Screen Content Equalization Home Screen content Explanation of items displayed Time Remaining Indicates the time left for equalization. Equalization runs for 60 minutes; time is counted down in 1 minutes increments until the Time Remaining displays 0 min. (During a precharge, the Time Remaining displays “n/a”— not applicable.) Battery Voltage Displays a range of 13.2 V to 18.0 with increments of 0.1V. Menu Pressing Menu returns you to Select Device screen.
Operation Terminating the Equalization Process The equalization process can be terminated in three ways: • • • user cancellation from the System Control Panel as shown in Figure 2-15 inverter/charger cancellation if AC is removed or the charger is disabled successful completion of the equalization process Operating Limits for Charger Operation The maximum output current for the MS2000 is 100 amps, split between the main charger (maximum 100 amps DC) and the Echo Charger (maximum 10 amps DC).
Operation Monitoring the MS2000 Indicator Lights The ten indicator lights on the front panel show you the operating status of the MS2000. A description of the lights is provided in Table 2-3. If none of the front panel lights are on, see “Troubleshooting Reference” on page 4–4. t Table 2-3 Front Panel Lights Light Illuminated Color Status Action or Status Item External AC Green When the MS2000 is connected to a qualified AC source or a generator, the External AC light illuminates.
Operation Faults and Warnings A fault affects the operation of the unit. A manual fault requires user intervention by clearing the condition and then pressing the Reset button on the inverter/ charger’s front panel. See the System Control Panel Owner’s Guide for information on clearing faults from the System Control Panel. A warning alerts you to a condition that could possibly affect operation of the unit.
3 Configuration Chapter 3, “Configuration” contains information about all configurable settings and procedures for the MS2000.
Configuration General Configuration Information System Control All changes to the configuration of the MS2000 are made with the System Control Panel (SCP). The System Control Panel provides configuration and monitoring capability for all Xanbus-enabled devices on the network. The front panel of the MS2000 provides limited control, including reset; main charger enable and disable; and inverter enable and disable. These functions can also be controlled from the System Control Panel.
Configuration System Menu Map Figure 3-1 provides a map of how the menus are organized. The order of devices appearing on the System Control Panel will vary, depending on the order in which they’ve been connected to the network.
Configuration Viewing the System Screen The System screen, as shown in Figure 3-2, is used to monitor system activity. You cannot select or change any of the information on the System screen. If you would like to view more detailed information, press Enter to go to the Select Device menu. menu Figure 3-2 MS2000 Float System Screen (Example) Viewing the Select Device Menu The Select Device menu is where you can view a list of all the Xanbus-enabled devices in your power system.
Configuration Selecting the MS2000 Basic Menu To select the MS2000 from the Select Device menu: 1. On the Select Device menu, MS2000 appears highlighted. 2. Press Enter. The MS2000 basic menu appears by default. Invert [*Enabled] Figure 3-4 MS2000 Basic Menu in Invert Mode Selecting and Adjusting the Configurable settings You can view MS2000 settings or change MS2000 settings from the MS2000 menu. Display settings show status items and cannot be changed.
Configuration MS2000 Configuration Menus The System Control Panel displays the MS2000 configuration menu in two formats: basic and advanced. The System Control Panel shows the MS2000 basic menu by default. MS2000 basic menu list status information and settings you may have to adjust on a routine basis. It provides access to basic control of the inverter/charger. MS2000 advanced menu settings require that you understand and plan for the changes you make.
Configuration The MS2000 menu structure is shown in Figure 3-6. The first four lines appearing in both menus: Mode, Battery, AC Input or AC Out, are status items only and are not configurable. Echo Chg Out in the Advanced Menu is also a status item and is not configurable.
Configuration MS2000 Device Menu The MS2000 device menu displays status information on the different modes of the inverter/charger. The first three lines of the device screen displays dynamic content that changes, depending on what operation mode that the MS2000 is in. Status information is not configurable; configurable items are indicated by square brackets [ ]. An asterisk indicates the value that was previously set. For example, in Figure 3-7, the MS2000 is in invert mode with AC current going out.
Configuration Table 3-1 Modes Mode Description AC Bypass AC input from an AC source like the utility grid or from a generator is allowed to pass through the unit to operate connected AC loads. The charger is not enabled but AC is qualified and passed through the unit. Equalize To improve the life and performance of a non-sealed, flooded (or wet) battery, the MS2000’s multi-stage charging cycle includes a manual equalize mode that can be used if recommended by the battery manufacturer.
Configuration MS2000 Menu (Basic) The MS2000 basic menu indicates the status of items and lists settings that you may have to adjust on a routine basis. If advanced menu is enabled, scroll through the MS2000 advanced menu items until Basic Menu is highlighted and press enter. This section describes each display item and configurable item in detail with an example of the line item.
Configuration Charger Configurable setting This setting lets you enable or disable the operation of the main charger. When the main charger is enabled and AC is connected to the input, the house battery bank will charge. The Echo Charger will charge if it is enabled separately in the Echo Charger menu. See “Echo Chg” on page 3–18. Important: Both the main charger and the Echo Charger must be set to enabled for the Echo Charger to operate.
Configuration Power Share Configurable setting Power Share is a configurable setting that you set to match to the breaker rating on the AC input. This setting is used to ensure that the charger limits its output to try to prevent nuisance tripping of the AC input breaker due to the total current drawn by the charger and your other AC loads. See also “Power Share” on page 2–22.
Configuration In the MS2000 home menu, highlight Equalize, as shown in Figure 3-8. [Enabled] [10.0A] [On] [Flooded] Figure 3-8 Equalize On When you select On, the equalization confirmation warning appears, as shown in Figure 3-9. Yes No Figure 3-9 Equalize Confirmation Warning Selecting Yes takes you to the equalization system home screen, as shown in Figure 3-10. Yes n/a 13.
Configuration Batteries must be fully charged before equalization. If they are not fully charged, a precharge occurs. During precharge, the Time Remaining appears as “n/a”—not applicable. When the equalization process begins, Time Remaining appears as a value between 60 min and 1 min. You can cancel the equalization process by selecting Cancel, in which case Figure 3-11 appears, asking if you want to cancel equalization.
Configuration Batt Type Full name Battery Type Configurable setting Select the type of battery for your house battery from Flooded, AGM, Gel or Custom. If a battery temperature sensor is not present, the MS2000 uses cold, warm or hot settings with the hot setting as the default. Batt Type [Flooded] Value Default Battery Type Flooded Flooded Custom AGM Gel When to use This setting is adjusted for the type of house battery you have.
Configuration Clear Faults Purpose Clear Faults is a command which clears all active faults in the MS2000. When faults are cleared, the device will resume normal operation. If the fault condition still exists, the fault will reoccur.
Configuration MS2000 Menu (Advanced) The MS2000 advanced menu lists settings that provide you with additional control over MS2000. However, you may not have to adjust these settings as part of regular operation. For a listing of advanced menu items, see “MS2000 Menu Structure — Overview” on page 3–7. These settings are only visible if Advanced Menu is selected. To select the MS2000 Advanced Menu, see “Selecting the MS2000 Advanced Menu” on page 3–20.
Configuration Max Chg Rate Full name Maximum charge rate Configurable setting The actual battery charge rate is determined by two things. First, the MS2000 uses the house battery Batt Size setting (C) on page 3–15 divided by 5 (C÷5) to determine that maximum total charger output. This value is then modified by the charge rate setting.
Configuration In another example where the bank size is 500 Ah or more and the Max Chg rate is set to 50%, the calculation would be: 500 ÷ 5 or 100 amps × 50%. The total output would be 50 amps with 40 amps going to the house battery bank and 10 amps to the engine battery. Load Sense Configurable setting This setting lets you enable or disable the load sensing function.
Configuration Selecting the MS2000 Advanced Menu The System Control Panel shows the MS2000 basic menu by default. If you would like to view the advanced menu, you must go to the System Settings menu and select Global Menus. Important: When you select Advanced on the Global Menu, the System Control Panel will display the advanced menus for all devices.To return to viewing the basic menu for any Xanbus-enabled devices, select Basic Menu from the advanced menu for that device.
Configuration Returning to MS2000 Basic Menu You can return to viewing the MS2000 basic menu by selecting Basic Menu from the MS2000 advanced menu. See “Basic Menu” on page 3–19.
Configuration Sub-Menus Configure Inv/Chg Menu (Configure Inverter/Charger Menu) Cfg/Inv Chg is a sub-menu. If selected, a list of sub-menu items appears. Lo DC Volt Full name Low DC input voltage shutdown Configurable setting This setting lets you set the low voltage shutdown level for the inverter. When to use Lo DC Volt [10.0V] Range Increment Default 10 to 13 volts 0.1 volt 10 volts This setting limits the depth of discharge on your house battery bank.
Configuration Sense Interval Configurable setting This setting lets you adjust the interval of load sensing. The longer the interval, the more power you will save. However, the longer intervals may cause delays in the inverter power up and starting your loads. Sense Interval [1s] Range of values Increment Default 1 second to 25 seconds 1 second 1 second Cfg AC Limits (Configure AC Limits) Cfg AC Limits is a sub-menu. If selected, a list of sub-menu items appear.
Configuration Eqz Volts Full name Equalization voltage Configurable setting This setting lets you set the desired equalization voltage. This menu is displayed only if charger equalization is enabled on the house battery bank. Select a setting based on the battery manufacturer’s recommendation. For more information, see “Battery Charging Reference for the Main Charger” on page B–1. Eqz Volts [15.5V] Range of values Increment Default 13.5 to 15.5 VDC 0.1 volts 15.
Configuration Cfg AC Limits (Configure AC Limits) CAUTION: Risk of damage to equipment The following configuration settings adjust the quality of the AC input source that the inverter/charger will qualify and pass through to your AC loads. Voltage or frequency that is too high or too low for a particular piece of load equipment may cause damage to that load. Before adjusting these settings, refer to the electrical rating of connected load equipment.
Configuration Outcome The lower frequency of voltage that will be qualified as “good” by the inverter/ charger can be varied. Hi AC Volt Full name Hi AC transfer voltage (AC over voltage level) Configurable setting This setting lets you adjust the voltage above which the inverter/charger no longer qualifies AC as “good” and attempts to transfer to Invert.
Configuration View Device Info Menu (Device Information Menu) The View Device Info menu allows you to view the Fault, Warning and Event logs. On the View Device Info menu, you can also restore the default setting for the MS2000. For a definition of faults and warnings, see “Faults and Warnings” on page 4–2. An event is an indicator of the system modes that the unit has been in. View Fault Log Display setting The Fault log displays the 20 most recent faults for your reference.
Configuration Restore Defaults Configurable setting The Restore Default command restores the default settings for each device. Restore Defaults When to use Adjust this setting when you wish to restore your settings to defaults. Important: Restoring to defaults will overwrite all of the stored values.
4 Troubleshooting WARNING: Electrical shock and fire hazard Do not disassemble the MS2000. It does not contain any user serviceable parts. Attempting to service the unit yourself could result in electrical shock or fire. The MS2000 is designed for high reliability of operation and has a number of protection features to provide trouble free operation. If, however, you have any problems operating your inverter/charger read this troubleshooting chapter.
Troubleshooting Faults and Warnings When a fault or warning message appears, you can acknowledge the message to clear the screen. To acknowledge a fault or warning message, press the Enter button on the System Control Panel. This action does not clear the fault or warning condition, so you should consult Table 4-3 and Table 4-4 for suggested actions after you have acknowledged the message. Refer to the System Control Panel Owner’s Guide for more information on faults and warnings.
Troubleshooting Warning Types There are two types of warnings: automatic and manual. When the MS2000 detects a warning condition, it displays a warning message on the System Control Panel. Table 4-2 describes how they differ in their behavior and in how you can respond to them when they appear on the System Control Panel. Table 4-2 Warning Types and Behavior 975-0125-02-01 Warning type Behaviour Automatic warning Clear automatically if the fault condition that generated the message goes away.
Troubleshooting Troubleshooting Reference This chapter provides you with troubleshooting tips to identify and solve most problems that can occur with the MS2000. This chapter is divided into the following four sections: 4–4 Section Page Number General Troubleshooting Guidelines See page 4–5. Warning Messages See page 4–6. Fault Messages See page 4–9. Inverter Applications (Loads) See page 4–15.
Troubleshooting General Troubleshooting Guidelines This section will help you narrow down the source of any problem you may encounter. Please read the following troubleshooting steps: 1. Check for a Warning or Fault message on the System Control Panel. See “Warning Messages” on page 4–6 and “Fault Messages” on page 4–9 for descriptions of these messages and the specific actions to take. If a message is displayed, record it before doing anything further. 2.
Troubleshooting Warning Messages Warning messages appear on the System Control Panel to alert you to an impending system change. You can retrieve and view the last ten warning messages using the control panel. The warnings have been recorded with a time stamp to let you know the date and time that the warning appeared. See “Warning Types” on page 4–3 for an explanation of automatic and manual warnings.
Troubleshooting Table 4-3 provides a detailed description of the warning messages and solutions. Table 4-3 Warning Messages Warning Number Message Warning Type W0 FET1 over-temp. Check airflow around it. W1 Cause Solution Automatic FET1 Over Temperature Warning Ensure adequate ventilation around the MS2000. Reduce the AC loads. FET2 over-temp. Check airflow around it. Automatic FET2 Over Temperature Warning Ensure adequate ventilation around the MS2000. Reduce the AC loads. W2 Bulk cap.
Troubleshooting Table 4-3 Warning Messages Warning Number Message Warning Type W9 Battery temp sensor not detected. Check connections. W10 Battery temp sensor failure. W11 Cause Solution Automatic Battery Temperature Sensor Not Present Install a battery temperature sensor (BTS). This warning will continue to display as long as no BTS is connected. Automatic Battery Temperature Sensor Shorted Replace battery temperature sensor. Batt voltage too high.
Troubleshooting Fault Messages When the MS2000 detects a fault condition, the fault is displayed on the System Control Panel and also is indicated by the illuminated red Fault light on the MS2000 front panel. A fault affects the operation of the unit. See “Fault Types” on page 4–2 for an explanation of the different fault types. You can view the 20 most recent fault messages of the MS2000 by selecting Fault Log from the Device Info menu in the MS2000 Advanced Menu.
Troubleshooting Table 4-4 provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or Customer Service. Table 4-4 Fault Messages Fault Number Message Fault Type Cause Solution F0 is too hot and has shut down. See guide. Automatic FET1 Over Clear the fault and attempt Temperature Shutdown restart. Ensure adequate ventilation around the MS2000. Reduce AC loads. F2 is too hot and has shut down.
Troubleshooting Table 4-4 Fault Messages Fault Number Message Fault Type Cause Solution F7 Too many AC loads. Turn some off, clear fault, try again. Clear the fault and attempt Escalating AC Overload (PEAK Auto Fault. CURRENT) Shutdown restart. Reduce AC loads. Must occur (AC OUTPUT) 3 times in 30 seconds before becoming a manual fault. F8 has lost input neutral connection. See guide. Manual Neutral loss shutdown Clear the fault and attempt restart.
Troubleshooting Table 4-4 Fault Messages Fault Number Message Fault Type Cause Solution F15 Input AC too low. Check source, clear fault, try again. Automatic AC Under Voltage Shutdown (AC Line 2 input) Not applicable to MS2000. F16 AC input frequency problem. Check gen for overspeed. Automatic AC Over Frequency Shutdown (AC Line 1 input) Clear the fault and attempt restart. Check AC input frequency. Check and adjust AC input high frequency setting. F17 AC input frequency problem.
Troubleshooting Table 4-4 Fault Messages Fault Number Message Fault Type Cause Solution F25 Reset the MS2000. If Escalating Auxiliary Power problem persists, call Auto Fault. Supply Over Voltage customer service. Must occur Shutdown 3 times in 30 seconds before becoming a manual fault. Clear the fault and attempt restart. If problem persists, call customer service. F26 Reset the MS2000. If Escalating Auxiliary Power problem persists, call Auto Fault. Supply Under Voltage customer service.
Troubleshooting Table 4-4 Fault Messages Fault Number Message Fault Type Solution Echo Charger Not Communicating Disable Echo Charger to stop this message from reappearing. F37 Echo Charger fault. Disable Echo Charger. F40 Reset the MS2000. If Manual problem persists, call customer service. No internal communication Service required. F41 Reset the MS2000. If Manual problem persists, call customer service. Dead battery charger timeout Try restarting dead battery charging once.
Troubleshooting Inverter Applications The Xanbus system performs differently depending on the AC loads connected to it. If you are having problems with any of your loads, read this section. The Xanbus system perform differently based on different loads. Resistive Loads These are the loads that the inverter finds the simplest and most efficient to drive. Voltage and current are in phase, which means they are in step with one another. Resistive loads usually generate heat in order to accomplish their tasks.
Troubleshooting drive these loads, either a small companion load must be used to bring the inverter out of its search mode, or the inverter may be programmed to remain on by defeating the search mode feature. Clocks The inverter’s crystal-controlled oscillator keeps the frequency accurate to within a few seconds a day. Most clocks do not draw enough power to trigger the load sensing circuit. In order to operate without other loads present, the load sensing will have to be defeated.
A Specifications Appendix A, “Specifications” contains the electrical and physical specifications for the MS2000 Sine Wave Inverter/Charger. All specifications are subject to change without notice.
Specifications Inverter Specifications All inverter specifications are at nominal conditions: ambient temperature of 77 °F (25 °C), 2000 watt resistive load, 12 volts DC inverting on the MS2000, 120 volts AC, unless otherwise specified.
Specifications Main Charger Specifications All charging specifications are at nominal conditions: ambient temperature of 77 °F (25 °C), 120 VAC, 60 Hz input, unless otherwise specified. Table A-2 Main Charger Specifications Charging method • Three-stage charge (Bulk, Absorption, Float) • Two-stage charge (Bulk, Absorption) The default charging method is three-stage.
Specifications Echo Charger Specifications Table A-3 Echo Charger Specifications Charging method Two-stage charge (Bulk, Absorption) Number of independent battery banks 1 Battery bank size 50 Ah or larger Charge voltage 14.3 VDC Charge current 10 A Battery voltage > 3 VDC Cut off current ≤ 1 A for 3 minutes Maximum charge time Stops automatically after 8 hours Input over voltage limit 18.
Specifications Environmental Specifications Table A-5 Environmental Specifications Nominal Ambient temperature 77 °F (25 °C) Full Power Operating Ambient Temperature Range –4 ° to 122 °F (–20 ° to 50 °C) Maximum Operating Temperature 140 °F (60 °C) Storage temperature range –40 ° to 185 °F (–40 to 85 °C) Humidity: Operation/Storage ≤ 95% RH, non-condensing Physical Specifications with Projections Table A-6 Physical Specifications Length 16.19 inches (411 mm) Width 14.
Specifications Invert Power Derating vs Ambient Temperature The inverter/charger delivers up to 2000 watts continuous of sine wave output to 50 °C ambient temperature and 1500 watts continuous of sine wave output to 60 °C ambient temperature, derated linearly from 50 °C to 60 °C. If the unit is in elevated ambient temperature above 50 °C, you are required to reduce power draw according to the Figure A-1 to avoid over-temperature shutdown.
B Battery Charging Reference for the Main Charger Appendix B, “Battery Charging Reference for the Main Charger” describes the multistage charging algorithm (formula) for the main charger of the MS2000.
Battery Charging Reference for the Main Charger Charging Algorithms (Formulas) Battery Type MS2000 charges flooded (or wet) lead-acid, gel, AGM (absorbed glass mat), and custom batteries. Flooded (or wet) Flooded (or wet) batteries have removable battery caps for refilling with distilled water and testing the electrolyte. Gel Gel batteries have the electrolyte in the form of a gel rather than a liquid and do not require topping up. Gel batteries are sealed and the battery caps are not removable.
Battery Charging Reference for the Main Charger Bulk Charge In the first stage—the bulk charge—MS2000 delivers its full-rated output current. This constant current is delivered to the batteries until the battery voltage approaches its gassing voltage—typically around 13.5 volts for 12 volt batteries. The bulk charge stage restores about 75% of the battery’s charge.
Battery Charging Reference for the Main Charger Equalization Charge The equalization charge must be manually initiated from the System Control Panel because it is not required each time the battery is recharged. Equalization is a deliberate overcharge designed to return each cell to optimum condition by reducing sulfation and stratification in the battery. The overcharge helps the battery to reach and maintain peak capacity.
Battery Charging Reference for the Main Charger Charge Algorithm Graph Bulk Absorption Float TCV TA TF VA VG VF1 VF2 IB IH Time Figure B-1 Three-Stage Charging Profile Charge Algorithm Definitions Table B-1 Battery Defaults Voltage Flooded (or wet) Gel AGM VA Absorption Voltage (VDC) 14.4 14.4 14.3 VG Gassing Voltage (VDC) 13.5 13.8 13.45 VF1 Float Voltage (VDC) 13.5 13.8 13.45 VF2 Float Exit Voltage (VDC) 12.5 12.5 12.5 VE Equalize Voltage (VDC) 15.
Battery Charging Reference for the Main Charger Time Flooded (or wet) Gel AGM ∆TF Float Timeout (days) 21 21 21 ∆TE Equalize Timeout (hours) 1 NA NA Important: The custom battery factory defaults are the same as for an AGM battery. AC Reconnect Summary If AC is disconnected during charging, the charge stage after AC is reconnected is indicated in Table B-2.
C Terminology This section provides a glossary of terms and a listing of abbreviations used in this guide.
Terminology Glossary Absorption Charge The second stage of three-stage battery charging. Voltage remains constant and current reduces as the battery becomes charged. This ensures complete charging. Alternating Current (AC) The type of electrical power supplied by the power utility or an AC generator. The unique characteristic of this form of electricity is that it reverses direction at regular intervals.
Terminology Engine Battery The engine battery is the battery connected to the Echo Charger output. Typically, this will be an engine starting battery or an auxiliary battery for loads other than the inverter. Float Charge The third stage of three-stage battery charging. After batteries reach full charge, charging voltage is reduced to a lower level to prevent gassing and to prolong battery life. This stage is often referred to as a maintenance charge.
Terminology Sine Wave The standard waveform of electric utility AC power. A sine wave is a rounded, smooth waveform alternating above and below zero volts. Surge Capacity The amount of current an inverter can deliver for short periods of time. Most electric motors draw up to six to ten times their rated current when starting. An inverter will “surge” to meet these motor-starting requirements. Most Xantrex inverters have surge capacities at least twice their continuous ratings.
Terminology Abbreviations Abbreviation Full name Definition A Ampere (Amps) See Glossary. ABYC American Boat and Yacht Council The ABYC is an American organization that publishes recreational boating safety standards. AC Alternating Current See Glossary. AGM Absorbed Glass Mat A type of battery in which the electrolyte or battery fluid is contained in glass-fibre mats between battery plates. Ah Ampere hour (amp hour) See Glossary.
Terminology Abbreviation Full name Definition SOC State of charge Indicates the quantity of electrical energy stored inside a battery. UL Underwriters Laboratory A standards writing and certification body which tests and approves products for regulatory compliance to international standards. THD Total Harmonic Distortion A measure of how pure or clean a waveform is. VAC Volts Alternating Current See Alternating Current in Glossary. VDC Volts Direct Current See Direct Current in Glossary.
Warranty and Product Information Warranty What does this warranty cover? This Limited Warranty is provided by Xantrex Technology, Inc. ("Xantrex") and covers defects in workmanship and materials in your MS2000 Sine Wave Inverter/Charger. This warranty period lasts for 24 months from the date of purchase at the point of sale to you, the original end user customer. You require proof of purchase to make warranty claims.
Warranty and Return What proof of purchase is required? In any warranty claim, dated proof of purchase must accompany the product and the product must not have been disassembled or modified without prior written authorization by Xantrex.
Warranty and Return SPECIFICALLY, PLEASE NOTE THAT THE MS2000 SINE WAVE INVERTER/CHARGER SHOULD NOT BE USED IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES. WITHOUT LIMITING THE GENERALITY OF THE FOREGOING, XANTREX MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE USE OF THE XANTREX MS2000 SINE WAVE INVERTER/CHARGER IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.
Warranty and Return Information About Your System As soon as you open your MS2000 Sine Wave Inverter/Charger package, record the following information and be sure to keep your proof of purchase. ❐ Serial Number _________________________________ ❐ Purchased From _________________________________ ❐ Purchase Date _________________________________ If you need to contact Customer Service, please record the following details before calling.
Index A absorption charge B–3 AC knockout illustrated 1–9 locations of 1–7 AC reconnect summary B–6 AC wiring compartment access panel 1–7 AGM (absorbed glass mat) batteries B–2 B batteries AGM (absorbed glass mat) B–2 custom B–2 flooded B–2 gel B–2 wet B–2 battery damage, risk of B–2 battery temperature sensor charger operation 2–17 features 1–11 illustrated 1–11 battery temperature sensor jack, described 1–9 battery types, description of B–2 bolt size DC terminal A–5 ground terminal A–5 bulk charge B–3
Index automatic 4–2 definition 2–24, 4–9 escalating automatic 4–2 manual 2–24, 4–2 fault types 4–2 faults and warnings 4–2 FCC compliance A–5 regulations x float charge B–3 Force Charge, defined 3–24 front panel described 1–7 illustrated 1–7 front panel light Charger ON 2–23 External AC 2–23 Fault 2–23 Inverter ON 2–23 Low Battery 2–23 Network 2–23 front panel lights and buttons described 1–8 illustrated 1–8 described 1–9 MS2000 advanced menu, selecting 3–20 MS2000 basic menu example of 3–5 returning to 3–
Index System Control Panel buttons described 2–3 function of 2–2 illustrated 2–6 using 2–3 system menu map 3–3 system mode operate 2–7 power save 2–7 system screen, example of 3–4 T three-stage charging algorithm B–2 three-stage charging profile, illustrated B–2 troubleshooting fault messages 4–9 general guidelines 4–5 motor loads 4–15 problem loads 4–15 resistive loads 4–15 warning messages 4–6 U Up arrow button 2–4 W warning automatic 4–3 definition 2–24 manual 4–3 warning types 4–3 warranty out of w
IX-4
Xantrex Technology Inc. 1 800 670 0707 Tel toll free NA 1 360 925 5097 Tel direct 1 800 994 7828 Fax toll free NA 1 360 925 5143 Fax direct customerservice@xantrex.com www.xantrex.