Quick Start Guide

38
When the heating/cooling stops, the fan shuts o󽗈 with a delay.
2. Compressor Protect Time
A time countdown to protect compressor to start frequently.
3. Compressor Min Outdoor Temp
When the outdoor temperature is below this temperature, the compressor
will not be used.
4. Compressor/(Aux) Heat min on time during heating/cooling cycles
5. Compressor/(Aux) Heat Stage 2 Temperature Delta
When the difference between the indoor temperature and the target
temperature reaches this value, the second stage is automatically turned
on.
6. Compressor/(Aux) Heat Stage 1 Max Runtime
If the first stage fails to reach the target temperature after this time, the
second stage will be automatically turned on.
7. Aux Heat Max Outdoor Temp
Auxiliary heat is turned on only when the outdoor temperature is below this
value.
Equipment Test: Test whether the corresponding function of the
equipment can run normally as required
Filter: Filter change reminder