Instruction Manual
PAGE 9
Residential Water Systems
CentriPro
Generation II – CentriPro 3-Wire Motors – Recommended Motor Lead Lengths
Motor Rating 60º C and 75º C Insulation - AWG Copper Wire Size
HP Volts kW FLA SFA 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0
0.5 115
0.37 8.8 10.9 101 160 255 404 629 1002 1591 2530 3192 4029 5076
0.5
230
0.37 5.3 6.1 359 571 912 1444 2246 3581 5685 9040 - - -
0.75
0.55 6.6 7.8 281 447 713 1129 1757 2800 4446 7070 8920 - -
1.0
0.75 8.1 9.4 233 371 592 937 1458 2324 3689 5867 7402 - -
1.5
1.1 9.1 10.9 201 320 510 808 1257 2004 3182 5059 6383 - -
2.0
1.5 9.9 12.2 180 286 456 722 1123 1790 2843 4520 5703 - -
3.0
2.2 14.3 16.5 133 211 337 534 830 1324 2102 3342 4217 5323 -
5.0
3.7 24 27 - - 206 326 507 809 1284 2042 2577 3253 -
3-WIRE, SINGLE PHASE 4" MOTORS - ELECTRICAL DATA, 60 HERTZ, 3450 RPM
Generation II – Released for sale in February/March 2012
Full Load Service Factor
Locked
Rotor
Amps
Winding
Resistance
Required
Control Box
1
Type
Order
No.
RJ Ref.
#
HP KW Volts SF Amps Watts Amps Watts
Main
(B-Y)
Start
(R-Y)
3-
Wire
with
Q.D.
Cap.
Start
Box
M05411 50C301 0.5 0.37 115 1.6
Y – 8.8
B – 8.8
R – 0
675
Y – 10.9
B – 10.9
R – 0
980 44
1.0 -
1.4
2.5 -
3.1
CB05411
M05412 50C311 0.5 0.37
230
1.6
Y – 5.3
B – 5.3
R – 0
740
Y – 6.1
B – 6.1
R – 0
1050 21
5.1 -
6.1
12.4 -
13.7
CB05412
M07412 75C311 0.75 0.55 1.5
Y – 6.6
B – 6.6
R – 0
970
Y – 7.8
B – 7.8
R – 0
1350 32
2.6 -
3.3
10.4 -
11.7
CB07412
M10412 100C311 1.0 0.75 1.4
Y – 8.1
B – 8.1
R – 0
1215
Y – 9.4
B – 9.4
R – 0
1620 41
2.0 -
2.6
9.3 -
10.4
CB10412
3-
Wire
with
CSCR
(CR)
or
Mag-
netic
Con-
tactor
(MC)
Con-
trol
Box
M05412 50C311 0.5 0.37 1.6
Y – 4.2
B – 4.1
R – 1.8
715
Y – 4.8
B – 4.3
R – 1.8
960 21
5.1 -
6.1
12.4 -
13.7
CB05412CR
M07412 75C311 0.75 0.55 1.5
Y – 4.8
B – 4.4
R – 2.5
940
Y – 6.0
B – 4.9
R – 2.3
1270 32
2.6 -
3.3
10.4 -
11.7
CB07412CR
M10412 100C311 1.0 0.75 1.4
Y – 6.1
B – 5.2
R – 2.7
1165
Y – 7.3
B – 5.8
R – 2.6
1540 41
2.0 -
2.6
9.3 -
10.4
CB10412CR
M15412 150C311 1.5 1.1 1.3
Y – 9.1
B – 8.2
R – 1.2
1660
Y – 10.9
B – 9.4
R – 1.1
2130 49
2.1 -
2.5
10.0 -
10.8
CB15412CR or
CB15412MC
M20412 200C311 2 1.5 1.25
Y – 9.9
B – 9.1
R – 2.6
2170
Y – 12.2
B – 11.7
R – 2.6
2660 49
1.6 -
2.2
4.8 -
5.9
2
CB20412CR or
CB20412MC
M30412 300C311 3 2.2 1.15
Y – 14.3
B – 12.0
R – 5.7
3170
Y – 16.5
B – 13.9
R – 5.6
3620 76
1.0 -
1.4
2.0 -
2.5
CB30412CR or
CB30412MC
M50412 500C311 5 3.7 1.15
Y – 24.0
B – 19.1
R – 10.2
5300
Y – 27.0
B – 22.0
R – 10.0
6030 101 .6 - .8
1.3 -
1.7
CB50412CR or
CB50412MC
¹ A CSCR control box with a CR sufx can be replaced by a Magnetic Contactor model ending in MC.
2
Prior to November 2012, the Winding Resistance was 10.8 – 12.0.
GENERATION II – 3-WIRE, 4" SINGLE PHASE RECOMMENDED WIRE LENGTHS