Manual

67
0215
0215 RAMP 1
4 sec
Ramp 1: Fast acceleration time
Possible settings: 1 – 250 (1000) sec
Excessively fast running up time may cause an error (OVERLOAD) during the HYDROVAR
starts up.
Excessively slow running up time may cause a drop of the outgoing pressure during
operation.
0220
0220 RAMP 2
4 sec
Ramp 2: Fast deceleration time
Possible settings: 1 – 250 (1000) sec
Excessively fast running down time tends to cause an error (OVERVOLTAGE).
Excessively slow running down time tends to generate over pressure.
0225
0225 RAMP 3
70 sec
Ramp 3: Slow acceleration time
Possible settings: 1 – 1000 sec
Excessively fast running up time may lead to oscillation and/or an error (OVERLOAD).
Excessively slow running up time can cause a drop of the outgoing pressure during
variation of the demand.
0230
0230 RAMP 4
70 sec
Ramp 4: Slow deceleration time
Possible settings: 1 – 1000 sec
Excessively fast running down time leads to oscillation of the HYDROVAR and thereby of
the pump.
Excessively slow running down time can cause pressure fluctuations during variation of
the demand.
0235
0235 RAMP FMIN A
2.0 sec
Ramp F
min
acceleration
Possible settings: 1.0 – 25.0 sec
Fast running up time to start up the HYDROVAR till the selected MIN. FREQUENCY [0250] is
reached.
Beyond the minimum frequency, RAMP1 [0215] (fast acceleration ramp) starts to work.
Excessively fast running up time may cause an error (OVERLOAD) during the HYDROVAR
starts up.