Examples:
Booster unit
Problem: no stop of the HYDROVAR
Parts to check measure
existing demand
non return valve is not closed
pre charge pressure in the pressure tank
incorrect setting of WINDOW and
RAMPHYSTERESIS
shut down ramp too slow
suction line too long
check pipes and valves
change non return valve
adjust according the diagram
set WINDOW [0310] (ca.10%) and
HYSTERESIS [0315] (80-50%)
set RAMP 2 [0220] to 4...13 sec.
the MINIMUM FREQUENCY [0250] should be
activated for pressure increase at 0 demand
Control on constant flow
Problem: control fluctuations
Parts to check measure
control characteristics are set too low
enlarger WINDOW [0310] and set
HYSTERESIS [0315] to 99% to control with
RAMP 3 and 4
Circulating pump
Problem: oscillation of the motor speed
Parts to check measure
control settings too fast
increase RAMP 3 [0225] and 4 [0230]:
100...200sec
WINDOW [0310] (ca.20%) and
HYSTERESIS [0315] (ca.99%)
Problem: ACTUAL VALUE can't be hold
Parts to check measure
HYSTERESIS is set too big HYSTERESIS [0315]: 90-99%
General
Problem: pressure fluctuations, analogue signal not constant
Solution:
check cables and connection of the screen
check earth connection of the transmitter cable
use screened cables