User guide
Installation Procedures
15
AQUAVAR
Switching Frequency
Max. Switching
Model
Watts Dissipated Watts Dissipated Watts Dissipated
Frequency for
AV2V-
at 4 kHz at 7 kHz at 10 kHz
Rated Current (kHz)
2S010D 37 44 51 10
2S020D 59 71 81 10
2S030D 77 92 106 10
2S050D 162 212 220 10
2S075D 195 251 271 10
2S100D 267 312 354 10
20010D 37 44 51 10
20020D 59 71 81 10
20030D 77 92 106 10
20050D 112 135 156 10
20075D 162 212 220 10
20100D 195 251 (1) — 6
20150D (2) (2) (2) (2)
20200D (2) (2) (2) (2)
40010D 33 43 53 10
40020D 52 69 84 10
40030D 68 90 110 10
40050D 99 131 161 10
40075D 112 144 174 10
40100D 139 180 217 10
40150D 170 210 255 (1) 9
40200D 200 245 — 7
40250D 280 383 — 7
40300D 335 371 (1) — 5
40400D 398 (1) — — 2.5
40500D 600 670 (1) — 5
40600D 710 (1) — — 4
40750D 720 (1) — — 2
50010D 40 52 64 10
50020D 62 83 101 10
50030D 82 108 132 10
50050D 85 115 155 10
50075D 91 131 172 10
50100D 112 160 — 8
50150D 164 — 282 (1) 9
50200D 218 277 (1) — 6
50250D 286 364 (1) — 6
50300D 343 388 (1) — 5
50400D 417 — — 4
50500D 700 — — 4
50600D 720 (1) — — 3
50750D 745 (1) — — 2
(1) Dissipation at rated current and
maximum switching frequency.
Electrical Connections continued
Table 2: Required Dissipation for Models Entirely Inside an Enclosure