User guide
Programming
51
At
Level 1
and
Level 2
, you enter the required value in percent from the
Second Additional
input
(20%) and (80%).
Intensity one and two depend on the
Sensor range
of the external value signal. The
Intensity 1
that
you have entered is valid until you reach
Level 1
, after reaching
Level 1
the
Required Value
has no
offset.
The
Required Value
is valid until you reach
Level 2
. After reaching
Level 2
, the new value, depending
on the
Intensity 2
, is valid.
Note that for most applications only one level and one intensity would be needed.
Press the key to advance to:
Use the and arrow keys to enter the % of the
additional input range where the first offset to the
required value will occur. The chart on the previous
page uses 20% as an example.
Press the key to advance to:
Use the and arrow keys to enter the % of the
additional input range where the second offset to
the required value will occur (if needed) The chart
on the previous page uses 80% as an example.
analogue value 1
Level 1
%
Intensity 1
- 10%
0%=4mA (0V/2V) 20%
60 PSI
80% 100%=20mA (10V)
required value
75 PSI
Intensity 2
- 20%
45 PSI
additional input 2
Level 2
%
LEVEL 1
XX.X%
LEVEL 1
20.0%
LEVEL 2
XX.X%
LEVEL 2
80.0%
▼
▼
*
▼
▼
*