User guide

Multiple Pump Constant Pressure... continued
12. Pump Address
In this section you will give the pump an address number. General-
ly, the first pump programmed will be number 1, the second will be number 2, and so
on. The purpose of this is to help the AQUAVARII controller sequence the start and
stop activity of the pumps in the system including the selection of lead and lag pumps.
• Hold the for 2 seconds to return to:
• Press again briefly to advance to:
• Press again for 2 seconds to display:
• Use the to select the address number.
(1, 2, 3 or 4)
13. Hold the for 2 seconds to return to:
• Press briefly to advance to:
• Press again to advance to:
• Set at 0% with
• Hold the for 2 seconds to return to
the Main Menu.
• At the Main Menu, advance to the screen:
• Press at the same time until the display
changes to:
14. Repeat steps 1 through 12 for each pump in the system. Use a different address
number for each pump.
57
Programming
SUBMENU RS485 INTERFACE
Screen
*
*
*
FREQ. LIFTING
LIFT INTENSITY 0%
SAVE ??? +
SAVE ??? SAVED
*
*
*
*
SUBMENU SEQ. CONTROL
SUBMENU RS485 INTERFACE
PUMP ADDRESS OFF
SAVE ??? +