User guide
77
Help Windows
Window text Help Text
Window Pressure window, percentage above and
5% below set pressure. See pages 61 and 62.
Ramp Hysteresis Hysteresis, part of the window.
50% See pages 61 and 62.
Ramp 1 Ramp 1: fast acceleration time. (Ramp up speed.)
4.0 Sec See page 62. Set higher for larger HP motors.
Ramp 2 Ramp 2: fast deceleration time. (Ramp down speed.)
4.0 Sec. See page 62. Set higher for larger HP motors.
Ramp 3 Ramp 3: slow acceleration time.
50 Sec. See page 62.
Ramp 4 Ramp 4: slow deceleration time.
50 Sec. See page 62.
Max. Frequency Maximum output frequency
60.0 Hz range: 6 - 70 Hz, see page 62.
Min. Frequency Minimum output frequency (range: 0 - max.
0.0 Hz frequency). See pages 43 and 63.
Config. F Min Configuration behavior at
f->0 or f->F Min minimum frequency, see page 63.
Stop-Delay Time Delay for pump stop when
0 Sec. f->0 is chosen, see page 63.
Sensor Adjust? Sensor zero adjustment (press inc + dec).
Out of Range See page 63.
Sensor Curve Sensor characteristic curve (linear is default).
(Linear or Quadratic) See page 63.
Sensor Range Normalize to maximum sensor value, adjust to
20mA = 25.0 bar (367.6 PSI) sensor’s maximum value. See page 63.
Mode: Mode: controller > pressure control;
Controller Actuator > frequency set point as ADC Value
Multicontroller > control of up to 4 pumps.
Synchronous > All motors synchronized for
same speed operation. See page 64.